Technical data
METTLER TOLEDO JAGXTREME Terminal Technical Manual
(9/00) 3-8
1. Market Sub-block
The JAGXTREME terminal is factory set for the market you specified when you ordered
the terminal. The Market sub-block lets you select a new country or market area and
limit parameters that affect legal-for-trade programming options.
1. Press ENTER at the Market? prompt to access this sub-block.
2. Press SELECT until the desired market area is displayed, then press ENTER.
Market areas include:
• USA—United States
• EC—European Community
• AUS—Australia
• CAN—Canada
• NONE—disables legal-for-trade option
3. Continue to the next sub-block, or press ESCAPE twice to exit the setup mode.
2. Scale Type Sub-block
The Scale Type sub-block prompts you for the number of internal scales and type of
scale that will be used.
1. Press ENTER at the Scale Type prompt to open the sub-block.
2. At the # Intrnl Scls? prompt, select the number of internal scales. Choose 1, 2,
3 or 4, (or 5 if a summing scale is desired), depending on the number of
scales connected to the JAGXTREME terminal.
When configuring terminals with two or more scales, select the first scale (A)
to calibrate by pressing SELECT (not in setup mode), then enter setup and
calibrate scale A. To calibrate the second scale you must exit setup mode,
select the second scale (B) with the SELECT key, then reenter setup and
calibrate scale B. Follow the same procedure for any additional scales.
3. Press SELECT at the Type? prompt until the desired scale type is displayed,
then press ENTER. Scale types include:
• Analog
• DigiTOL (bench or portable)
• DigiTOL Junction Box (J-Box)
• UltraRes High
• UltraRes Low
• POWERCELL
• High Precision (MMR/IDNET)
• None
• Summing
If Analog is Selected
Select board #1 (BD1) or board #2 (BD2), depending on the address of the Analog
PCB connected to the scale. Jumper W3 on the Analog PCB determines the board
address. If two analog PCBs are installed, they must have different board addresses. If
two dual analog cards are installed, you may also select board #3 and board #4.
Market
Select Market
USA, EC, AUS, CAN, NONE
You can exit the setup mode any
time during configuration. You
may need to press ESCAPE several
times to return to the EXIT Setup?
p
rom
p
t, then
p
ress ENTER.
Scale Type
Internal Scale
Select scale type
Location of Scale
Connection
JAGXTREME terminals with a single
analog scale must use Board #1
(BD1). When the board is selected.
The JAGXTREME terminal proceeds to
the next sub-block.