High Temperature Threshold: The high temperature alarm threshold in degrees F.
Min: -67 F; Max: +302 F
Default: +150 F (Effectively Disabled); Disable: 0x8000 (From host only.)
Low Temperature Threshold: The low temperature alarm threshold in degrees F.
Min: -67 F; Max: +302 F
Default: -50 F (Effectively Disabled); Disable: 0x8000 (From host only.)
Local Display Mode: Enable Local Display mode to configure the CTM to transmit ISM
radio data packets to a local display device. Disable if not used to maximize battery life.
Range: Enable or Disable
Default: Disabled
ISM Transmitter Number: Sets the transmitter number of the CTM. The local display
device will display this number next to the displayed tank level. This feature is very useful
in multiple tank applications.
Min: 1; Max: 127 (Maximum of 8 on handheld and current local display devices.)
Default: 1; Disable: N/A
Application Configuration Parameters
General
The WESROC
®
RMS Industrial LTE Cellular Tank Monitor (CTM) application (tank level)
configuration parameters can be modified using the WESROC
®
RMS Portable Diagnostic
Unit (PDU). These configuration parameters can also be modified by the WESROC
®
RMS
Host System (Host) during a report.
Parameter List
Sensor Scaling: The sensor output scaling to be used to calibrate the CTM to the type of
tank and gauge being monitored.
Min: 1; Max: 255 (Not all used at this time – see current list below.)
Default: 1 (Small horizontal tank dial.); Disable: N/A
1 = Std Horiz (small dial horizontal propane or fuel tank)
2 = Lg Dial (large dial horizontal tank - use on large dials with black Rochester sensor)
3 = 420# Vert (420# vertical propane cylinder)
4 = 200# Vert (200# vertical propane cylinder with Taylor type “A” dial)
5 = Liquid CO2 (vertical liquid CO2 cylinder – do not use, special use only)
6 = Fuel Horiz (small dial horizontal fuel tank – no longer used, use Std Horiz scaling)
7 = Flat (no dial scaling correction – used with hydrostatic CTM on a vertical tank)
8 = 20k Horiz (20k gallon horizontal fuel tank – do not use, special use only)
9 = 4-20mA (monitor 4-20mA industrial current loop – special use only)
10 = ITC LgDial (large dial horizontal tank - use on large dials with ITC Precision Sensor)
13 = RoundHoriz (used with hydrostatic CTM on a round horizontal tank)