User's Manual

WESROC
®
RMS Cellular Tank Monitor - Operation Manual - Independent Technologies, Inc.
72-70-164, Rev. P4 Page 19 06/16/2011
High Temperature Threshold: The high temperature alarm threshold in degrees F.
Min: -67 F; Max: +302 F
Default: +150 F (Effectively Disabled); Disable: 0x8000 (From host only.)
Low Temperature Threshold: The low temperature alarm threshold in degrees F.
Min: -67 F; Max: +302 F
Default: -50 F (Effectively Disabled); Disable: 0x8000 (From host only.)
Local Display Mode: Enable Local Display mode to configure the CTM to transmit data
packets to a local display device. Disable if not used to maximize battery life.
Enable or Disable
Default: Disabled
ISM Transmitter Number: Sets the transmitter number of the CTM. The local display
device will display this number next to the displayed tank level. This feature is very
useful in multiple tank applications.
Min: 1; Max: 127 (Maximum of 8 on handheld and current local display devices.)
Default: 1; Disable: N/A
Application Configuration Parameters
General
The WESROC
®
RMS Cellular Tank Monitor application (tank level) configuration
parameters can be modified using the WESROC
®
RMS Portable Diagnostic Unit (PDU).
These configuration parameters can also be modified by the WESROC
®
RMS Host
System (Host) during a report.
Parameter List
Sensor Scaling: The sensor output scaling to be used to calibrate the CTM to the type
of tank and gauge being monitored.
Min: 1; Max: 255 (Not all used at this time – see current list below.)
Default: 1 (Small horizontal tank dial.); Disable: N/A
Std Horiz (small dial horizontal tank)
Lg Dial (large dial horizontal tank) (Use on large dials with black Rochester sensor.)
420# Vert (420# vertical cylinder)
200# Vert (200# vertical cylinder with Taylor type “A” dial)
Liquid CO2 (liquid CO2 vertical cylinder – special use only)
Fuel Horiz (small dial horizontal fuel tank)
Flat (no dial scaling correction – special use only)
20k Horiz (20k gallon horizontal fuel tank – special use only)
ITC LgDial (large dial horizontal tank) (Use on large dials with ITC Precision Sensor.)