User`s guide
6-11
When the next screen appears, select the Data Collection process.
Figure 6-11
DC-2000 Process Selection List
In the next screen (Figure 6-12) select the Internet Ports tab. If there is not already an
ANSI server installed, select the ADD button. In the next screen select the following:
6.4.1 Enabled Checkbox
Check this box.
6.4.2 Internet Address
This is the Internet address that the DCM-200 will use to make the connection. This
address was programmed into the unit using MP32 software, as described in Chapter-5.
The administrator of the data collection system usually assigns this address.
6.4.3 Port Type
Select ANSI Server.
6.4.4 Port Number
When ANSI Server is selected as the Port Type, the port number is automatically set to
50465. This must match the port number that was programmed into the DCM-200 (see
Chaper-5).
6.4.5 MAX Connections
This is the number of devices that are allowed to make a connection at the same time.
The maximum is 255, but this is shared with other DC-2000 Internet applications on the
same system. For instance, if another application is set for 200 connections, then the