5.1 Insulation resistance
5.1.1 Insulation resistance measuring procedure
Insulation resistance measurement is performed in order to assure safety against electric
shock through insulation. It is covered by the EN 61557-2 standard. Typical applications
are:
Insulation resistance between conductors of installation,
Insulation resistance of non-conductive rooms (walls and floors),
Insulation resistance of ground cables,
Resistance of semi-conductive (antistatic) floors.
See chapter 4.1 Function selection for instructions on
key functionality.
Figure 5.1: Insulation resistance
Test parameters for insulation resistance measurement
Uiso Test voltage [100 V, 250 V, 500 V, 1000 V, 2.5 kV]
Limit
Minimum insulation resistance [OFF, 0.01 MΩ ÷ 200 MΩ]