Operation Manual
MD 9225 Clamp Meter Series Operation
10
Note: In DCA measurements, hysteresis of the jaws (after measuring high DC currents)
may introduce non-zero residual readings. Relative Zero
mode should be used each
time to offset the residual readings, if any, for more accurate measurements.
Adjacent current-carrying devices such as transformers, motors and conductor wires will
affect measurement accuracy. Keep the jaws away from them as much as possible to
minimize influence.
Resistance, and Continuity functions
CAUTION
Using Resistance, Continuity or Diode function in a live circuit will produce false results
and may damage the instrument. In many cases the suspected component must be
disconnected from the circuit to obtain an accurate measurement reading
Inputs are made through the test leads terminals. Slide-switch on defaults at . Press
SELECT
button momentarily to select Continuity function which is convenient for
checking wiring connections and operation of switches. A continuous beep tone
indicates a complete wire.
Diode test function
Inputs are made through the test leads terminals. Slide-switch on defaults at .
Press
SELECT
button momentarily 2 times to select Diode test function. Normal forward
voltage drop (forward biased) for a good silicon diode is between 0.400V to 0.900V. A
reading higher than that indicates a leaky diode (defective). A zero reading indicates a
shorted diode (defective). An OL indicates an open diode (defective). Reverse the test