Installation Manual

A3-MT300
16
RH Calibration Interface:
Relative Humidity Calibration Interface and Operation Instructions When MT300SP Is Not
Connected
UP key: No function
DOWN key: No function
OK key: The system returns to the setting
interface when this key is pressed
Menu key: The system returns to the setting
interface when this key is pressed
Interface and Operation Instructions Upon MT300SP Humidity Calibration Failure
UP key: Press this button to add the value by
0.1% and press and hold this button to add the
value by 1%
DOWN key: Press this button to reduce the
value by 0.1% and press and hold this button to
reduce the value by1%
OK key: Start calibration again
Menu key: The system returns to the setting
interface when this key is pressed (the
calibration fails and the system does not save
the calibrated value)
Interface and Operation Instructions Upon Successful MT300SP Humidity Calibration
UP key: Press this button to add the value by
0.1% and press and hold this button to add the
value by 1%
DOWN key: Press this button to reduce the
value by 0.1% and press and hold this button to
reduce the value by1%
OK key: Start calibration again
Menu key: The system returns to the setting
interface when this key is pressed (the system
will save the calibrated value automatically)
Note:
1. RH calibration setting range: From 10.0% to 99.9%;