Owner's manual

Flow
Appears in Flow mode only. Press È to R Function and Æ to select Pump, LoAlm
(low alarm) or HiAlm (high alarm).
Pump mode - press È and Æ and set relay On and Off set point.
LoAlm mode - press È and set relay On point. Relay will be energized with levels
below the On point and de-energized with levels above the On point.
HiAlm mode - press È and set relay On point. Relay will be energized with levels
above the On point and de-energized with levels below the On point.
LOE - press Æ to select Off ÆOn Æ Hold. In a loss of echo condition, the
(Loss Of Echo) relay will turn Off (de-energize), On (energize) or Hold its current state.
Each relay can be individually configured. Press È.
ALT permits relays calibrated in Pump mode to be
alternated automatically. Pump alternation
allows even pump wear in pumping station
applications.
ALT (-None-) indicates that no relays have
been programmed in Pump mode.
ALT 123 - Press Æ to place cursor (underline)
under the relay number to be programmed for
alternation and press Ç or È to highlight.
Repeat until all relays to be alternated are
highlighted.
Press È to
Store? Yes and Æ to Yes. Press Ç or È to save your Relay settings.
AquaMetrix
Ultrason
Page 14
PUMP ALTERNATI
O
N (R1, R2, R3)
LEAD
PUMP
LAG
PUMP 1
LAG
PUMP 2
1st CYCLE
2nd CYCLE
3rd CYCLE
...ETC
1
2
2
3
3
1
3
1
2