Action Value Action Parameters Description
DIVA, ccc,
aaa
Divide “ccc” by the accumulator value of “aaa” and
place the result in “ccc”. Where “aaa” and “ccc”
accumulator (A1-A24).
The default destination IDs for messages created by the actions above are
set via the DESTINATION, d1 {, d2 {, d3 {, d4}}} command. When a single ID
of “0” is given in a Meteor Burst network that uses the MCC-520B for a
Master Station, the messages are sent to the network host system for
routing via the source routing system. In a Line-of-Sight network, using
MCC-545Cs as Base and/or Repeater Stations, then a single ID of “1” is used
for routing to the Host via any Base or Repeater.
5.6.8 Reading Internal Sensor Values
The MCC-545C -03 and later radios have the capability to read certain
sensor values, including the internal rechargeable battery, internal
temperature of the unit, etc.
Following are the most commonly used commands to read these sensor
values:
Command Description
EVENT,STATUS,TEMP
Reads the internal temperature of the unit
EVENT,STATUS,BAT
Reads the unloaded battery (external) of the radio
EVENT,STATUS,LBAT
Reads the loaded battery (external) of the radio
EVENT,STATUS,IBAT
Reads internal NiMetal Hydride rechargeable battery
EVENT,STATUS,ADC1
(through ADC6)
5.6.9 Common Command Parameters
a. settle
settle is the number of clock ticks required “at or above” the event level
to trigger an event. Valid range: 1 - 65535. This corresponds to a range of
62.5 milliseconds to 1 hour, 8 minutes and 16 seconds. For discrete events,
the event level is “high” or “1”. For analog events, the level is given in
engineering units.