User manual

TD990200-0ME
45
Press the Configure button.
Select the Port settings tab.
Set the Bits per second to 19200.
Set the Data bits to 8.
Set the Parity to None.
Set the Stop bits to 1.
Set the Flow control to None.
Press the OK button.
Select the Settings tab.
Choose the “Terminal Keys” option.
In the Emulation box select ANSI.
Press the OK button.
If you connect to a running Embedded Metasys Ethernet Router you
may need to refresh the screen. While the router program is
executing press “R” to redraw the screen.
Using File Transfer Program
Since the Embedded Metasys Ethernet Router has no floppy disk, a
file transfer program is required to load new files or change existing
files. The program XFER.EXE is a command line DOS file transfer
program that supports the Xmodem protocol. The program resides
on the router and can communicate with HyperTerminal. Two
arguments must be passed when executing the program from the
host computer (running HyperTerminal) to indicate direction of
transfer and the filename. For example, to transfer a file to the
router from the host type in at the DOS prompt the following:
xfer in filename.ext
Once you hit return the program awaits the transfer. From the menu
bar, select Transfer and then Send File. In the dialog box enter the
file name and its path. Be sure to select Xmodem protocol. Select
Send and the file will transfer. Upon completion, you will need to
reboot the router.
To reverse the process, type in at the DOS prompt the following:
xfer out filename.ext
This time select Receive File from the Transfer menu. A dialog box
will appear. You will need to specify a folder for receiving the file.
Again verify that Xmodem protocol is selected. Select Receive and
the transfer will be made. Rebooting will again be required.