User manual

TD990200-0ME
43
The Invalid counters indicate the number of Invalid messages
received. An Invalid message is a message that contains an invalid
address. The Invalid counters should always be zero during normal
operation. If the Invalid message counter is ever non-zero, the latest
Invalid message will display on the monitor screen, below the
statistics information.
The ARCNET Failure counter indicates the number of times an
ARCNET message could not be delivered to its destination due to
Ethernet errors. While this counter should normally be zero, it will
increment if one of the other Metasys Ethernet Routers is offline.