This is normal. The two PWR lights should be on, but the
Communication Processor should have no lights on.
The Communication Processor will test its memory and then execute
its AUTOEXEC.BAT file. This will take less than a minute. You
will observe a message that will allow you to halt the booting process
in order to access the Ethernet Router Configuration screen. Hit any
key during this pause and the screen will be displayed. At the
bottom of the screen there are instructions on what keys to press to
perform certain editing tasks.
The left side of the screen displays information to be loaded into the
SOCKET.CFG file. This is the Metasys Ethernet Router IP address,
Subnet Mask and Existing LAN Router IP address.
On the right side of the screen is data that is written to the
ROUTER.CFG file. This information includes switches (e.g., /S)
and all ARCNET subnet addresses with corresponding Metasys
Ethernet Router IP addresses. This information, except the switch
settings, must be identical on all Metasys Ethernet Routers.
There is a provision for setting the Extended Timeout value of the
ARCNET subnet. The default is 0 and in the majority of
applications, it should be left at 0 meaning normal timeouts.
Extended timeouts are only required on large fiber optic installations
where the ARCNET network diameter exceeds 5 km.