User`s guide

Specifications and Technical Data A-3
Specifications
Table A-2: DX LCD Display Specifications and Technical Data
Supply Voltage
24 VAC +15%/-10% or
9 to 18 VDC from DC power supply (AC adapter)
Power Consumption
4 VA at 24 VAC or
2 VA with DC power supply (AC adapter)
Ambient Operating
Conditions
0 to 50°C (32 to 122°F)
10 to 90% relative humidity non-condensing
30°C (86°F) maximum dew point
Ambient Storage
Conditions
-20 to 60°C (-4 to 140°F)
10 to 90% non-condensing relative humidity
30°C (86°F) maximum dew point
Processor
Motorola® 68HC11D0
Memory
256 Kbytes flash memory
Terminations
Separable terminal block for 1-1.5 mm
2
(16 AWG [maximum]) cables for 24 VAC
supply and alarm contacts. Universal jack connection for DC power supply.
Standard RJ11 phone jack for serial connection to the DX controller. (Cable and
DX/PC adapter are supplied with DX LCD Display. IU-9100 and MM-CVT
adapters are ordered separately. See Ordering Codes.)
Display and Keypad
LCD display with 16 lines by 40 characters (240 x 128 pixels)
Screen size: 110 x 60 mm (4.3 x 2.4 in.)
Sealed membrane touch keypad with eight keys
Alarm Indicator
Red LED flashes to indicate alarms. Beep tone can be activated for audible
indication.
Alarm Contacts Rating
35 V AC/VDC at 1 ampere
Mounting
Direct wall mount and panel mounting kits (See Ordering Codes)
Housing
Material: ABS + polycarbonate (GE CYCOLOY), self-extinguishing UL94V-0.
Protection: IEC529
Applications: IP30 for hand-held and wall mounting
IP42 for panel mounting applications
Dimensions (H x W x D)
150 x 180 x 47 mm (5.91 x 7.09 x 1.85 in.)
Serial Cable Length
Approximately 2.7m (9 ft) (stretched out)
DX Communication
Cable/Wiring
9600 baud asynchronous, half duplex via 6-pin RJ12 telephone style jack
0.09 mm
2
(28 AWG) phone cable
Maximum 15m (50 ft )(RS-232C)
Shipping Weight
0.78 kg (1.72 lb)
Agency Listing
CE Directive 89/336/EEC: EN 50081-1, EN 50082-1
UL and CUL per UL916, and CSA
FCC Part 15 - Class A - CISPR22B
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.