Operating the DX LCD Display 4-37
2. Use the and keys to page through the four screens of
parameters for the two modules. Figure 4-25 shows the second
screen of parameters for the first Optimal Start/Stop module.
dxtk_34
FLOOR 8 AHU 11:40
ALARM:
OPTIMAL START 1
Tota l:00
Minimum Startup (Min) = 120.0
Maximum Startup (Min) = 240.0
Maximum Optimal Stop (Min) = 240.0
Start Mode Bldg Factor Heating = 5.0
Start Mode Bldg Factor Cooling = 5.0
Stop Mode Bldg Factor Heating = 100.0
Stop Mode Bldg Factor Cooling = 100.0
Adaptive Filter (%) = 10.0
Outdoor Design Heating = -10.0
Outdoor Design Cooling = 30.0
Control Range = 2.0
Time Schedule Connection = TS2
Figure 4-25: Optimal Start/Stop Screen (Page 2 of 2)