User`s guide

4-36 Display Terminals
6. Press again to confirm the new value. The next value of the
period begins to flash to indicate that it can be changed
(e.g., the Start day).
7. Repeat Steps 5 and 6 for each value of the period until you have
edited all values of the period. The last press of the
key
completes the edit sequence for the period and the new values are
sent to the DX controller.
Note: Press the
esc
key at any time to abort the edit sequence.
8. Repeat Steps 3 to 7 for the next parameter you want to change, or
press the
esc
key to return to the Main menu.
Changing Optimal Start/Stop Parameters
To change Optimal Start/Stop parameters:
1. Select the Optimal Start/Stop option in the Main menu. The first
screen of the first Optimal Start/Stop module appears, as shown in
Figure 4-24.
dxtk_33
FLOOR 8 AHU 11:40
ALARM:
OPTIONAL START 1
Tota l:00
OVR OS1 OFF
Operating Mode = Heating and Cooling
Zone Temperature = 16.6
Outside Air Temperature = 15.3
Zone Temperature SetPt = 20.0
Calculated Startup Time (Min) = 96.0
Stop Mode Bias = -3.0
Current = Not Active
Status = Disabled
Adaptive = Disable
Figure 4-24: Optimal Start/Stop Screen (Page 1 of 2)
Note: As shown in the example screen above, the Optimal
Start/Stop module can be manually overridden to On or Off,
which is indicated by the OVR status at the beginning of the
first line.