User`s guide
Operating the DX LCD Display 4-29
Viewing the Alarm Summary
To view the Alarm Summary:
1. Select the Alarm Summary option in the Main menu. The first of
eight Alarm Summary screens appears, as shown in Figure 4-19.
dxtk_28
FLOOR 8 AHU ALM SUMMARY 1/8 11:40
HA Room Temperature 24.5 Deg C
ALM Chiller1 Thermal Alarm
ALM Humidifier S/S Fault
ALARM: Humidifier S/S ALM Total:03
Figure 4-19: Alarm Summary Screen
The data shown for each point in the Alarm Summary is the same
as in the Point Data. The order in which the points are listed is
also the same as in the Point Data screens, i.e., it is the order in
which the points were defined in the display configuration, and
does not indicate the times at which the alarms occurred. Use the
Alarm Log to see the relative times of occurrence (see Viewing the
Alarm Log in this chapter).
2. Use the and keys to page through the Alarm Summary
screens. You can page through all eight screens, although only the
first few screens may contain alarm summary data.
3. Press the
esc