Table of Contents DX LCD Display User’s Guide Using This Guide .......................................................1-1 Chapter 1 Introduction...................................................................................................... 1-1 Key Concepts................................................................................................... 1-2 Chapter Organization .....................................................................................................
Display Terminals Detailed Procedures........................................................................................ 3-7 Mounting the DX LCD Display on a Wall .......................................................................3-7 Mounting the DX LCD Display on a UPM ......................................................................3-9 Mounting the DX LCD Display in a Panel ....................................................................3-10 Cabling a Permanently Mounted Device......
Table of Contents 3 Adjusting and Overriding Points...................................................................................4-25 Releasing Overridden Points .......................................................................................4-28 Viewing the Alarm Summary ........................................................................................4-29 Viewing the Alarm Log .................................................................................................
DX LCD Display User’s Guide 1-1 Chapter 1 Using This Guide Introduction The DX LCD Display User’s Guide provides information about how to use the DX LCD Display. This chapter outlines the guide’s organization and content. © May, 2000 Johnson Controls, Inc. Code No. LIT-6364120a www.johnsoncontrols.
1-2 Display Terminal Key Concepts Chapter Organization Each chapter of this DX LCD Display User’s Guide is divided into four sections as described in Table 1-1. Table 1-1: Chapter Organization Section Description Introduction Briefly outlines the contents of the chapter. Key Concepts Describes background information necessary to perform or understand specific tasks. Procedure Overview Describes general steps for performing the tasks described in the Detailed Procedures section.
DX LCD Display User’s Guide 2-1 Chapter 2 Introduction to DX LCD Display Introduction The DX LCD Display unit is a person/controller interface used with the DX-9100 series of controllers. The display can act as a simple adjust and indication unit or be used for more complex tasks often associated with a workstation. The display is designed for the maintenance person who needs a straightforward way to monitor and adjust points in a controller without being limited in capability.
2-2 Display Terminals Key Concepts DX LCD Display Figure 2-1 shows the DX LCD Display. Dxlcd_1 Figure 2-1: DX LCD Display Use the display as either a portable, hand-held unit for use with more than one controller, or it can be permanently mounted on the wall, on a Universal Packaging Module (UPM) or in a panel as an integral part of the controller application. Features The DX LCD Display: • Stores up to eight configurations.
Introduction to DX LCD Display 2-3 • Indicates alarms both visually and audibly. • Maintains an Alarm Summary of points currently in an alarm state. • Maintains an Alarm Log of the last 96 alarm and return-to-normal Changes-of-State (COSs) with time and date stamp. For the Alarm Log feature to operate as described, the DX LCD Display must be permanently connected to one DX controller. • Displays Trend Data collected in the DX controller (if supported by the controller).
2-4 Display Terminals Note: In the remainder of this guide, the DX-9100 and DX-9120 controllers are referred to simply as DX controllers. Display Configurations Each DX LCD Display unit stores up to eight display configurations. Different configurations customize the display as required for different applications or situations.
Introduction to DX LCD Display 2-5 Related Information This guide describes how to install and operate the DX LCD Display. Refer to Table 2-1 for additional information on configuring the DX LCD Display, and installing and configuring DX-9100 controllers: Table 2-1: Related Information Description Document Configuring the DX LCD Display GX-9100 Software Configuration Tool LIT-6364060 (FAN 636.4 and 1628.
2-6 Display Terminals
DX LCD Display User’s Guide 3-1 Chapter 3 Installing the DX LCD Display Introduction Use the DX LCD Display as either a portable device, or permanently mount it in a panel or on the wall. For panel and wall mounting applications, the display unit is permanently connected to one DX controller or to an N2 Bus with up to eight DX controllers.
3-2 Display Terminals Key Concepts Mounting Options Mount the DX LCD Display in a standard enclosure or standard cabinet door, such as the range of Universal Packaging Modules (UPMs) from Johnson Controls (shown in Figure 3-1).
Installing the DX LCD Display 3-3 Considering Unit Dimensions Figure 3-2 shows the overall dimensions of the DX LCD Display. For panel cutout dimensions or wall bracket drill hole spacing, see Detailed Procedures in this chapter. 143 mm (5.63 in.) 47 mm (1.85 in.) 180 mm (7.09 in.) esc ! 173 mm (6.81 in.) 150 mm (5.91 in.
3-4 Display Terminals Internal Wiring of Adapters for Serial Communications Cable Figure 3-3 shows the internal wiring of the adapters available for the DX LCD Display serial communications cable. The DX/PC adapter is provided with the DX LCD Display unit. The IU adapter (Europe) or the CVT adapter (North America) is required for N2 communications. Order the IU and CVT adapters separately. See Ordering Codes in Appendix A Specifications and Technical Data.
Installing the DX LCD Display 3-5 Procedure Overview Table 3-1: Installing the DX LCD Display To Do This Follow These Steps: Mount the DX LCD Display on a Wall Attach the wall mounting bracket to the wall and place the display unit onto the bracket. Connect the serial cable and power supply to the display. Attach the display unit to the mounting bracket. Connect the serial cable from the display to the DX controller and apply power.
3-6 Display Terminals To Do This (Cont.) Follow These Steps: Cable a Permanently Mounted Device (Cont.) To establish the N2 Bus connection: Plug the connector on one end of the serial communications cable into the DX LCD Display. Plug the other end of the serial communications cable into the 9-pin adapter marked IU for the IU-9100 in Europe, or into the 25-pin adapter marked CVT for the MM-CVT101 in North America.
Installing the DX LCD Display 3-7 Detailed Procedures Mounting the DX LCD Display on a Wall Note: A separately available wall mounting kit is required to mount the DX LCD Display on a wall (see Ordering Codes in Appendix A). To mount the DX LCD Display on a wall: 1. Drill appropriate holes for the wall mounting bracket using the dimensions shown in Figure 3-4. 76 mm (3.0 in.) 20 mm (0.79 in.) 6 x 30 mm (0.24 x 1.18 in.) dxtk_6 Figure 3-4: Wall Mounting Bracket 2.
3-8 Display Terminals 4. Place the DX LCD Display on the bracket, as indicated by in Figure 3-5. Note: The springs of the bracket fit into the rounded cavities in the back of the display. Align the slots in the bracket and the slots in the sides of the display unit. 2 1 3 Dxtk_7 Figure 3-5: Securing the DX LCD Display to the Wall 5.
Installing the DX LCD Display 3-9 Mounting the DX LCD Display on a UPM To mount the DX LCD Display on a UPM: 1. Position the wall mounting bracket on the UPM to allow mounting of the DX LCD Display (Figure 3-6). 2. Mark four mounting holes. 3. Mark a cable hole. 4. Drill four pilot holes for mounting the base (hole size should be between 0.160 inch and 0.170 inch, bit size No. 18, 19, or 20). 5. Drill a 1/2 inch hole for communication and power cables. 76 mm (3.00 in) Washer 20 mm (0.
3-10 Display Terminals 11. Attach the unit to the UPM. See Figure 3-5. 12. Apply power. Mounting the DX LCD Display in a Panel The panel mounting kit, supplied as standard equipment with the DX LCD Display, is required to mount the display in a panel or cabinet door. To mount the DX LCD Display in a panel or cabinet door: 1. Make an appropriate cutout in the panel or cabinet door using the dimensions shown in Figure 3-7 (note the maximum panel thickness shown in the figure).
Installing the DX LCD Display 16 mm Maximum (0.63 in. Maximum) 3-11 174 mm (6.85 in.) 1 144 mm (5.67 in.) Panelmt Figure 3-7: Panel Mounting Dimensions Note: If the panel thickness is greater than 5 mm (0.19 in), remove the flap on the back of the display covering the erminals (see Figure 3-10) prior to mounting the display. 2. Insert the DX LCD Display into the cutout, as indicated by in Figure 3-7. 3.
3-12 Display Terminals 2 3 2 3 Panelbac Figure 3-8: Securing the DX LCD Display in the Panel 4. Secure the DX LCD Display in the panel by tightening the screws of the locking tabs, as indicated by in Figure 3-8. 5. From the rear of the panel, connect the serial cable between the DX controller and the display unit, and connect the power supply to the display. Refer to Cabling a Permanently Mounted Device in this chapter.
Installing the DX LCD Display 3-13 Cabling a Permanently Mounted Device Establishing a Direct Connection to the DX Controller Figure 3-9 shows the connections made to the DX LCD Display for power and communications with the DX controller.
3-14 Display Terminals To establish a direct connection to a DX controller: 1. Lift the flap covering the connectors on the back of the DX LCD Display as Figure 3-10). Cover Figure 3-10: Connector Location 2. The serial communications cable has a telephone-type connector on each end. Plug one end of the cable into the phone jack labeled RS232 INPUT on the DX LCD Display (Figure 3-11).
Installing the DX LCD Display 5. If required, wire the alarm contacts (Pins 94-96) to the external annunciation device (alarm horn). The circuit voltage must not exceed 35 VAC/VDC. Note: 6. 3-15 The alarm contacts are provided only on the DX LCD Display, Version 3 (DT-9100-8104). The VDC supply voltage already available at the DX controller can power the DX LCD Display. Wire a supply voltage cable to Pins 91-93, using the 24 VAC pin assignments shown in Figure 3-11.
3-16 Display Terminals 4. Set the S1 switch on the modem circuit board to DCE (Modem 1). 5. Set the RTS/DTR control jumper to DIS position. See Figure 3-13. Jumpers Ground DCE TXTX+ RDRD+ DIS RTS/DTR Control S1 Switch DTE dtmodjmp Figure 3-13: Modem Jumper and Switch Settings 6. Plug the telephone-type connector on one end of the DX LCD Display serial communications cable into the phone jack labeled RS232 INPUT on the DX LCD Display. 7.
Installing the DX LCD Display 3-17 DX-9100/9121 Controller 9-pin Connector 9 to 25-pin Modem Cable (Maximum 15 m (50 ft) Modem 1 (Transmit+)TX+ (Transmit -) TX(Receive +) RX+ 25-pin (Receive-) RXConnector } Pair 1 } Pair 2 Maximum 15 m (50 ft) Total Cable Length Modem 2 from Modem 2 to DX LCD Display (Receive +)RX+ (Receive -) RX(Transmit +)TX+ (Transmit -) TX- 25-pin 9 to 25-pin Modem Cable Connector 4-Wire Cable (Maximum distance: 3.
3-18 Display Terminals Establishing an N2 Bus Connection Figure 3-15 shows the DX LCD Display on the N2 Bus. IU-9100 Converter (or MM-CVT) DX LCD Display DX-9100 DX-9100 DX-9100 DX-9100 N2 Bus dtn2bus Figure 3-15: Devices on the N2 Bus To establish a connection to the N2 Bus: 1. Lift the flap covering the connectors on the back of the DX LCD Display. 2. Plug one end of the telephone-type connector on the serial communications cable into the phone jack labeled RS232 INPUT on the DX LCD Display.
Installing the DX LCD Display 3-19 Cabling a Portable Device Figure 3-16 shows the connections between the DX LCD Display and a DX controller. DX-9100/9120 Controller DX LCD Display Unit esc ! Serial Cable RS-232 Serial Port Connector 9/12 VDC Power Supply (AC Adapter) dtportca Figure 3-16: Connections to the DX LCD Display To establish a connection to a DX controller: 1. Lift the flap covering the connectors on the back of the DX LCD Display. 2.
3-20 Display Terminals
DX LCD Display User’s Guide 4-1 Chapter 4 Operating the DX LCD Display Introduction The DX LCD Display is operated through a simple keypad and menu system interface that provides easy, intuitive access to the data and parameters stored in the DX controller. It provides password protection for those functions that change data in the DX controller, such as adjusting/overriding point values, editing time schedules, and changing optimal start/stop parameters.
4-2 Display Terminals Key Concepts Display and Keypad The DX LCD Display includes a sealed membrane touchpad, and a 240 by 128 pixel Liquid Crystal Display (LCD) that shows up to 16 lines of text with 40 characters per line. Figure 4-1 shows the layout of the front panel of the DX LCD Display. Table 4-1 shows Display Screen Components, Table 4-2 and Table 4-3 describe the keypad.
Operating the DX LCD Display 4-3 Display Screen Certain areas of the display screen always show the same type of information during normal operation (i.e., once the DX LCD Display has selected a display configuration). These areas of the screen are indicated in Figure 4-1 and described in Table 4-1. Table 4-1: Display Screen Components Area Description Name of Display Configuration Lists the name of the current configuration.
4-4 Display Terminals Keypad Figure 4-2 shows the layout of the sealed membrane keypad: esc dxtk_9 Figure 4-2: Keypad Table 4-2 describes the keypad keys and symbols, and Table 4-3 describes the Light-Emitting Diode (LED) indicator located in the center of the keypad. Table 4-2: Keypad Keys Name Symbol Description Up/Down Move between lines on a page, for example, to move the selection bar through different items in a menu.
Operating the DX LCD Display 4-5 Menu System Power On (Diagnostic Self Test) Same DX as Last Connected? Yes No esc Twice (Double Click) to Reset Choose Controller* Last Screen Home Page or esc esc Main Menu and to highlight to select Alarm Summary (page 1 of 8) Point Data (page 1 of 8) esc Alarm Log (page 1 of 24) Trend Data esc Alarm Summary (page 2) Point Data (page 2) esc esc esc esc Password esc and Analog Trend Alarm Log (page 24) esc Optional Start/Stop Holidays Alarm Log
4-6 Display Terminals Home Page The DX LCD Display shows a graphical Home Page as the default screen when it is moved to a different controller. Each of the eight display configurations can have a different Home Page. The Home Pages are customizable, and can contain live point data from the DX controller. The default Home Page is shown in Figure 4-4. For more information on defining custom Home Pages, see GX-9100 Software Configuration Tool Technical Bulletin (LIT-6364060).
Operating the DX LCD Display 4-7 Point Data The DX LCD Display stores up to eight separate display configurations. Each configuration specifies up to 96 points of the DX controller that can be displayed and monitored by the DX LCD Display. The point data is shown on up to 8 pages (or screens) of 12 points per page. On power up, the display attempts to select a display configuration to match the DX controller configuration. It uses a default display configuration if it cannot find a match.
4-8 Display Terminals The override command changes the value of a point whose values are set by the controller through an automatic control process. Override the point to prevent the controller from changing its value. This can be thought of as a manual override of the automatic control process. A release command must be sent to the point to return it to automatic control (see Releasing Overridden Points in the Detailed Procedures section).
Operating the DX LCD Display 4-9 Alarm Log The Alarm Log shows the history of the last 96 alarms that have occurred in your system and the date and time of their occurrence. In addition to the alarm Change-of-State (COS), the log also shows the return-to-normal COS. This allows you to tell at a glance when alarms occurred and when they returned to their normal state. Note: The Alarm Log can only show alarms on the points included in the display configuration that are defined as alarms, i.e.
4-10 Display Terminals Time Schedules The DX controller stores eight time schedules used to schedule actions on a weekly basis. Each schedule defines up to eight time slots. Each time slot defines a start time, a stop time, and one or more weekdays. When the current day and time-of-day agree with all of the conditions of any time slot, the output of the corresponding time schedule is set to On. The DX LCD Display can be used to view and edit the schedules of the connected DX controller.
Operating the DX LCD Display 4-11 Trend Data If the connected DX controller supports Trend, it can collect and store Trend data for up to 12 analog and logic variables. An analog variable corresponds to an analog item in the DX controller, such as an analog input. A logic variable in the DX controller is a byte value representing eight digital bits, such as the eight digital inputs DI1 to DI8. Trend data is collected for all eight bits of the logic variable.
4-12 Display Terminals Viewing and Editing Analog Trend If you selected an analog trend variable in the main Trend Data screen, the Analog Trend Data screen appears, showing a graphic plot of the data available from the DX controller in Figure 4-5. GROUND FLOOR TREND 5 11:40 Green Room Temp SAMPLE: Actual 06 June 1997 13:23 23.4 Deg C 100 Auto 0 More...
Operating the DX LCD Display 4-13 The plot itself is shown as a continuous line of up to 61 points, where each point represents one sample. If any sample falls outside of the range, then that sample point will not be displayed and there will appear to be a break in the plot. The range values can be adjusted, however, to make all samples visible in the same graph. The procedure for editing the range values is described later in this chapter.
4-14 Display Terminals The Trend Group screen shows a menu with the names of the individual bits of the digital variable (i.e., logic variable byte), as defined in the display configuration. The third line of the screen shows the name of the trend variable. Note: In Figure 4-6, the number 4 in the menu means that the fourth bit was not given a name in the display configuration, so its number was used as the default name. This may mean that the bit is not used.
Operating the DX LCD Display 4-15 Procedure Overview Table 4-4: Operating the DX LCD Display To Do This Follow These Steps: Establish Communication with a DX Controller Connect the serial cable between the display and the controller. Connect the cord of the power supply adapter to the display and plug the adapter into an AC wall socket. to For direct connect, when the power-on self-test is complete, press continue.
4-16 Display Terminals Detailed Procedures Establishing Communication with a DX Controller To establish communication with a DX controller: 1. Connect the serial cable between the display and the controller. See the Installing the DX LCD Display chapter for details. 2. Connect the cord of the power supply adapter to the display and plug the adapter into an AC wall socket. See the Installing the DX LCD Display chapter for details. Note: There is no power switch on the DX LCD Display.
Operating the DX LCD Display 4-17 3. Press the key to continue when the power on self test is complete. If you do not press a key, the screen is cleared after a five second delay. The next screen that appears depends on whether you have connected the display to a different DX controller or whether it is still connected to the same controller to which it was connected the last time it had power. If it is a different controller, the Home Page for the active configuration appears.
4-18 Display Terminals If a controller’s configuration does not match one of the predefined configurations in the display unit, the default configuration is used (if enabled) for that controller. To choose and connect to a DX via the N2 Bus: 1. Use the and keys to choose the desired controller. 2. Press the key to confirm your selection. The Home Page for the selected controller appears.
Operating the DX LCD Display 4-19 Displaying the Main Menu To display the Main menu: 1. Press the esc key from any screen to display the Main menu (Figure 4-10). Note: Some screens are sub screens of other screens, in which case pressing the esc key returns you to the parent screen. To reach the Main menu, keep pressing esc until the Main menu appears. Be careful, however, not to press esc too quickly because you might inadvertently reset the display.
4-20 Display Terminals Displaying the Home Page To display the Home Page: 1. From the Main menu, select the Home Page option. The Home Page defined in the current display configuration appears. 2. If the multiple Home Page feature is enabled, you can press the and keys to page through the Home Pages. 3. When the desired Home Page/Configuration name appears in the screen, release the or key. After a two second delay, the corresponding Home Page appears. 4. Press the Notes: key to return to the Main menu.
Operating the DX LCD Display 4-21 Entering a Password To enter a password: 1. Select the Password option in the Main menu. The Password screen appears, as shown in Figure 4-11. Initially the first digit of the password is set to zero and it flashes to indicate that it can be changed. 11:40 FLOOR 8 AHU Enter Password: 0**** Total:00 ALARM: dxtk_20 Figure 4-11: Password Screen 2. Press the or key to increase or decrease the value of the first digit to correspond to your password. 3.
4-22 Display Terminals FLOOR 8 AHU 11:40 Password Incorrect Monitor Only Total:00 ALARM: dxtk_21 Figure 4-12: Incorrect Password, No Clearance (Monitor Only) 11:40 FLOOR 8 AHU Password Correct Modify Points ALARM: Total:00 dxtk_22 Figure 4-13: Level 2 Clearance (Modify Data Points)
Operating the DX LCD Display 4-23 11:40 FLOOR 8 AHU Password Correct Modify Points and Time Schedules Audible Alarm: On Total:00 ALARM: dxtk_23 Figure 4-14: Level 1 Clearance (Modify Data Points and Time Schedules) 5. Press the key to return to the Main menu. If you have Level 1 clearance, you can change the setting of the audible alarm before returning to the Main menu, as described under the next heading.
4-24 Display Terminals Viewing Point Data To view point data: 1. Select the Point Data option in the Main menu. The first of up to eight Point Data screens appears, as shown in Figure 4-15. FLOOR 8 AHU 11:40 POINT DATA 1/8 Status HA Description Digital (Binary) Value OVR Analog/Counter Value Analog/Counter Units Room Temperature 24.5 Deg C Room Set Point 21.0 Deg C Supply Air Temp 28.8 Deg C Mixing Dampers 25.0 % Heating Coil 15.0 % Cooling Coil 0.
Operating the DX LCD Display 4-25 As indicated in Figure 4-15, the data shown for each point is: • status of the point (See Table 4-6.) • description of the point as defined in the display configuration • current value of the point • units for analog and counter values If any point in the Point Data screens has a status other than normal, a status text is shown to the left of the point description. This allows you to determine which points require your attention.
4-26 Display Terminals FLOOR 8 AHU HA OVR POINT DATA 1/8 Room Temperature 25.8 Deg C Room Set Point 24.0 Deg C Supply Air Temp 17.5 Deg C Supply Fan On Return Fan On Mixing Dampers 10.0 % Heating Coil 0.0 % 75.0 % Cooling Coil Supply Filter Clean Outside Air Temp Electric Meter ALM 11:40 Humidifier S/S ALARM: Room Temperature HA 29.7 Deg C 1234567 KWattH Fault Total:02 dxtk_25 Figure 4-16: Highlighted Point (Its Value Can Be Changed) 3.
Operating the DX LCD Display FLOOR 8 AHU HA POINT DATA 1/8 25.8 Deg C Room Set Point 24.0 Deg C 17.5 Deg C Mixing Dampers 10.0 % Heating Coil 0.0 % Cooling Coil 75.0 % Supply Fan On Return Fan On Supply Filter Clean Outside Air Temp Electric Meter ALM 11:40 Room Temperature Supply Air Temp OVR Humidifier S/S 4-27 29.7 Deg C 1234567 KWattH Fault ALARM: Room Temperature HA Total:02 dxtk_26 Figure 4-17: Highlighted Value 5. Use the and keys to change the value.
4-28 Display Terminals Releasing Overridden Points To release overridden points (shown as OVR status on the Point Data screens): 1. Select the point you want to release on the Point Data screens as described in Steps 1 to 4 of the Adjusting and Overriding Points section). When you press to confirm the selection (Step 4), the highlight moves from the point description to the OVR status (see Figure 4-18). The OVR status begins to flash to indicate that it can be changed.
Operating the DX LCD Display 4-29 Viewing the Alarm Summary To view the Alarm Summary: 1. Select the Alarm Summary option in the Main menu. The first of eight Alarm Summary screens appears, as shown in Figure 4-19. FLOOR 8 AHU ALM SUMMARY 1/8 HA Room Temperature ALM Chiller1 Thermal ALM Humidifier S/S ALARM: Humidifier S/S 11:40 24.5 Deg C Alarm Fault ALM Total:03 dxtk_28 Figure 4-19: Alarm Summary Screen The data shown for each point in the Alarm Summary is the same as in the Point Data.
4-30 Display Terminals Acknowledging Alarms Note: When an alarm occurs, the red LED above the Alarm symbol on the keypad begins to flash, and if enabled, an intermittent beep tone begins to sound. (In the DX LCD Display, Version 3, DT-9100-8104, the alarm contacts are also activated.) These indicate an unacknowledged alarm. The Alarm and Total fields at the bottom of the display also change to show the new alarm. To acknowledge the alarm (silence the beep tone and stop the LED from flashing): 1.
Operating the DX LCD Display 4-31 The entries in the Alarm Log are listed chronologically from most recent to oldest. The data shown for each point in the Alarm Log is the same as in the Point Data screens, with the addition of the time of occurrence at the end of the line. The status fields of return-to-normal entries show the text NOR, instead of being blank, to make them easier to recognize. Dates on which there were no occurrences are not shown in the log.
4-32 Display Terminals Setting the Clock To set the clock: 1. Select the Time/Date option in the Main menu. The Time/Date screen appears and the Time parameter is highlighted, as shown in Figure 4-21. FLOOR 8 AHU TIME/DATE 11:40 Time: 11:40 Date: March 24, 2000 Daylight Saving Date: Start: End: March 30 Oct 26 ALARM: Total: dxtk_30 Figure 4-21: Time/Date Screen 2. Use the and keys to move the highlight bar to the parameter you want to change. 3.
Operating the DX LCD Display 4-33 Editing Time Schedules To edit time schedule: 1. Select the Time Schedules option in the Main menu. The first of eight Time Schedule screens appears, as shown in Figure 4-22. FLOOR 8 AHU OVR TIME SCHEDULE 1 Time Schedule1 ON Extension Status OFF Forced Status NONE Extension Time 30.
4-34 Display Terminals The values of the parameters shown on the Time Schedule screen are read from the DX controller. The first three parameters show the current status of the time schedule, as described in Table 4-7: Table 4-7: Time Schedule Status Parameter Possible Values Status Description Field Name of Time On and Off Schedule OVR The name of the time schedule is defined in the display configuration. The value shown is the current output state of the time schedule.
Operating the DX LCD Display Note: 8. 4-35 Press the esc key at any time to abort the edit sequence. Also, numbers are used to indicate weekdays in the Days parameter. The numbers 1 to 7 are Monday through Sunday, and 8 is any day defined as a holiday in the DX controller (see the Defining Holidays section). Repeat Steps 3 to 7 for the next parameter you want to change, or press the esc key to return to the Main menu. Defining Holidays To define holidays: 1.
4-36 Display Terminals 6. Press again to confirm the new value. The next value of the period begins to flash to indicate that it can be changed (e.g., the Start day). 7. Repeat Steps 5 and 6 for each value of the period until you have edited all values of the period. The last press of the key completes the edit sequence for the period and the new values are sent to the DX controller. Note: 8. Press the esc key at any time to abort the edit sequence.
Operating the DX LCD Display 4-37 2. Use the and keys to page through the four screens of parameters for the two modules. Figure 4-25 shows the second screen of parameters for the first Optimal Start/Stop module. FLOOR 8 AHU Minimum Startup (Min) OPTIMAL START 1 Maximum Startup (Min) = 240.0 Maximum Optimal Stop (Min) = 240.0 Start Mode Bldg Factor Heating = 5.0 Start Mode Bldg Factor Cooling = 5.0 Stop Mode Bldg Factor Heating = 100.0 Stop Mode Bldg Factor Cooling = 100.
4-38 Display Terminals The values of the various parameters shown on the Optimal Start screens are read from the DX controller. Table 4-8 gives a short description of the Optimal Start/Stop parameters. Refer to DX controller documentation if further explanation is required. Table 4-8: Optimal Start/Stop Parameters Parameter Description Zone Temperature This number, expressed in degrees, is the desired zone temperature at the scheduled occupancy time.
Operating the DX LCD Display 4-39 3. Use the and keys to move the highlight bar to the parameter you want to change. 4. Press the key to begin the edit sequence for the selected parameter. The first part of the parameter begins to flash to indicate that it can be changed. For example, the number to the left of the decimal point begins to flash. 5. Use the 6. Press again to confirm the new value. The next part of the parameter begins to flash to indicate that it can be changed (e.g.
4-40 Display Terminals The main Trend Data screen shows a menu with the names of the 12 trend variables as defined in the display configuration. 2. Use the and keys to move the highlight bar to the trend variable you want to view. Trend 8 in Figure 4-26 is an example of a mismatch between the trend variable definitions in the display and controller configurations. The highlight bar skips over Trend 8 to prevent you from selecting it. 3. Press the key to confirm your selection.
Operating the DX LCD Display 4-41 Viewing Digital Trend To view Digital Trend: 1. Use the and keys to move the highlight bar to the bit you want to view, or press the esc key to return to the main Trend screen. 2. Press the key to confirm your selection. The first of up to eight Digital Trend Data screens appears, as shown in Figure 4-27.
4-42 Display Terminals If no COS events were recorded for this bit throughout the time during which Trend data was collected, the screen shows the message No Changes. The DX controller stores a maximum of 30 samples for any logical variable byte, and it stores a new sample if any single bit changes. 3. Use the screens. and 4. Press the screen.
DX LCD Display User’s Guide A-1 Appendix A Specifications and Technical Data Introduction This appendix contains ordering and specification information. Table A-1 lists ordering codes, and Table A-2 lists product specifications. © May, 2000 Johnson Controls, Inc. Code No. LIT-6364120e www.johnsoncontrols.
A-2 Display Terminals Key Concepts Ordering Codes Table A-1: Ordering Codes Code Description DT-9100-8104 DX LCD Display unit with Version 3 firmware and alarm contacts output (includes panel mounting kit, serial communications cable, and DX/PC plug adapter) DT-9100-8902 Wall mounting kit for DX LCD Display unit DT-9100-8903 Replacement panel mount kit DT-9100-8904 Plug adapter for MM-CVT converter DT-9100-8905* Plug adapter for IU-9100 converter DT-9100-6801 Replacement serial communication
Specifications and Technical Data A-3 Specifications Table A-2: DX LCD Display Specifications and Technical Data Supply Voltage 24 VAC +15%/-10% or 9 to 18 VDC from DC power supply (AC adapter) Power Consumption 4 VA at 24 VAC or 2 VA with DC power supply (AC adapter) Ambient Operating Conditions 0 to 50°C (32 to 122°F) 10 to 90% relative humidity non-condensing 30°C (86°F) maximum dew point Ambient Storage Conditions -20 to 60°C (-4 to 140°F) 10 to 90% non-condensing relative humidity 30°C (86°F)
A-4 Display Terminals Notes Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 www.johnsoncontrols.com Release 8.0 Printed in U.S.A.