Specification
Specifications and
dimensions subject to
change without notice.
Eaton
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
24GRLED
Catalog No. Wt. Pallet
24GR-LD5-48 20 lbs. 28
SHIPPING DATA
SAMPLE NUMBER: 24GR-LD5-48-F1-UNV-L835-CD1-U
NOTES:
(1)
An EQ Grid Clip is recommended for all 9/16" ceiling systems.
(2)
Products also available in non-US voltages and frequencies for international markets.
(3)
Not available when specifying emergencies, voltage must be
specific.
(4)
With integral test switch/indicator/laser test. For approximate delivered lumens multiply the lumens per watt of the desired fixture by the wattage of the emergency battery pack (100 lm/W x 7=700 lumens).
IES-format photometry for luminaire under emergency operation available.
(5)
Gasketing only available with aluminum door frame.
(6)
Gasketing minimum .125.
(7)
Step dimming (bi-level) 1 driver, 4200 - 10000, 2 driver, 12000
and up lumen model.
(8)
DALI available from 4200 - 9000 lumen models. Two drivers required for 10000 lumen models and up.
(9)
Requires two drivers for 10000 lumens and above.
(10)
Used to bypass local control during outage.
Must be used in conjunction with UL 1008 device (provided by others). GTR2 option includes 2 relays on fixtures with dimming drivers. ETRD option only requires one relay when used on a dimming fixture. Must specify
voltage as 120V or 277V when ordering these devices.
(11)
Nominal lumen output. See table for actual values
(12)
SR driver required for LWIPD1 only. PDR required for 120 lumens and up.
(13)
DesignLights Consortium® Qualified
and classified for both DLC Standard and DLC Premium, refer to www.designlights.org for details.
(14)
XMFR required for 15000 lumens and up.
(15)
347V versions are not available with emergency options. SD, 5LTD, and SR
drivers with 347V are available but not DLC qualified.
(16)
A19/156 lens creates holographic effect on the surface of the lens.
LED Lumen Output
(11)
30=3000
34=3400
38=3800
42=4200
48=4800
56=5600
64=6400
72=7200
85=8500
90=9000
ACCESSORIES
EQ-CLIP-U=T-BAR Safety Earthquake Clips
(1)
DF-24-W=2' x 4' Drywall Frame Kit
ISHH-01=Programming Remote for Integrated Sensor
(D)
ISHH-02=Personal Control Remote for Integrated Sensor
(D)
100=10000
120=12000
130=13000
150=15000
180=18000
Rating
[Blank]=
Standard
ATW-SW4=
Chicago
Rated
Series
(13)
R=General Purpose Troffer
Width / Length
24=2' x 4'
Trim Type
G=Grid/Lay-in
(Standard)
(1)
G=Concealed T
G=Slot Grid
Door Frame
Standard=Flat White Steel Door
(Leave Blank)
FA=Flush White Extruded
Aluminum c/w Spring Latch
RA=Regressed White Extruded
Aluminum
FAN=Flush Natural Anodized Extruded Aluminum
RAN=Regressed Natural Anodized Extruded Aluminum
FAB=Flush Black Extruded Aluminum
RAB=Regressed Black Extruded Aluminum
A/WG=Prismatic Acrylic Lens, Wireguard & Doorframe
F1/WG=Frosted Prismatic Acrylic Lens, Wireguard & Doorframe
LED Type
LD5=LED 5.0
Shielding
F1=A12 .095 HP (Standard)
F125=A12 .125 HP
A=A12 .095
A125=A12 .125
A19/156=#19 Pattern Acrylic
(.156" Thick)
(16)
FGW080=Frosted Glazed
Lens .080
Voltage
(2)
347V=347 Volt
(14), (15)
UNV=Universal Voltage 120-277
(3)
48V=48 Volt Low-voltage (Class 2)
Options
CCT
L830=3000K
L835=3500K
L840=4000K
L850=5000K
Flex
A3/8-4/18GDIM=3/8" Flex with 0-10V Dimming Leads
Multiple other configurations available. See below for details.
GL=Single Element Fuse
GM=Double Element Fuse
Emergency
EL7W=7-watt, 120V-277V emergency
battery pack installed
(4)
EL14W=14-watt 120V-277V emergency
battery pack installed
(4)
ELV7W=7-watt, DLVP-compatible low voltage
emergency battery pack installed
(C)
ELV14W=14-watt DLVP-compatible low voltage
emergency battery pack installed
(C)
GTR2=Bodine Generator Transfer Relay
(10)
ETRD=Iota Emergency Transfer Relay with
dimming control
(10)
Options
PAF=Painted After Fabrication
G1=Gasket, Door Frame and
Housing
G2=G1 plus Gasket between
Lens and Door
G3=G1 and G2 plus Gasketing
on Mounting Surface of
Fixture Trims
(5), (6)
XFMR=Transformer
Driver Type
CD=0-10V Dimming Driver
(10%-100% Dimming)
(9)
HCD=0-10V Dimming Driver
(1%-100% Dimming)
(9)
SR=Sensor-ready Dimming Driver
for LWIPD1 option
(1%-100% Dimming)
(12), (B)
5LTD=Fifth Light DALI Driver
(10%-100% Dimming)
(8), (E)
5LTHD=Fifth Light Dimming Driver
(1%-100% Dimming)
(E)
LV1=DLVP Dimming Driver
(0%-100% Dimming)
(C)
SD=Step Dimming Driver
(50% or 100% Dimming)
(7)
LH=Lutron HiLume (LDE1 series) 1%-100% EcoSystem Driver
with Soft-on Fade to Black dimming
(F)
L5=Lutron 5 Series (LDE5-Series) 5%-100% EcoSystem Driver
(F)
Number of Drivers
1=1 Driver
2=2 Drivers
Integrated Sensing Systems
SWPD1=WaveLinx Wireless Integrated Sensor
(A)
LWIPD1=LumaWatt Pro Wireless Integrated Sensor
(B)
LWTPD1=LumaWatt Pro Wireless Tile-mount Sensor
(B)
SLVPD1=DLVP Low-voltage Integrated Sensor
(C)
SVPD1=0-10V Stand-alone Integrated Sensor
(D)
Integrated Sensing and Control System Options
NOTES: Integrated options must be used in conjunction with the associated system and may not be compatible with other options or accessories. Please refer to the following:
(A)
Consult WaveLinx system pages for
additional details and compatibility.
(B)
Consult LumaWatt Pro system pages for additional details and compatibility.
(C)
Consult DLVP system pages for additional details and compatibility.
(D)
Consult SVPD series system
pages for additional details and compatibility.
(E)
Consult Fifth Light system pages for additional details and compatibility.
(F)
Consult Marketplace Options - Lutron system pages for additional details and compatibility.
Compatible only with driver series shown, and may require two or more drivers. Requires field commissioning to operate or dim. Contact Lutron at www.lutron.com.
Packaging
U=Unit Pack
PAL=Job Pack, out of carton
PALC=Job Pack, in carton
ORDERING INFORMATION
Flexible Metal Conduit Options
Flex options available for 0-10V dimming control, DALI dimming control, emergency and night light functions. 72-inch factory-in
stalled and pre-wired to driver, fitted to luminaire housing access plate with 90° enclosed FMC
connector. Not all options may be combined and installation ratings vary by type.
A3/8-4/18GDIM series notes:
Factory installed dimming option 3/8” flexible metal conduit with 2-#18 power and ground wires and 2-#18 UL-listed jacketed 0-10V +/- control wires. Meets UL 66, 83, 1479, 1569, 1581, 2556.
NEC® 250.118, 300.22(C), 392, 396, 330, 501, 502, 503, 530, 504, 505, 518, 520, 530, 645, 72; Federal Specification A-A-59544 (f
ormerly J-C-30B); all applicable OSHA and HUD Requirements. UL Classified 1-, 2-, and 3-hour
through penetration with applicable fire stop product (not included). May be surface mounted, fished and/or embedded in plaster.
Cable tray and approved raceway rated, install per NEC®; Environmental Air-Handling Space
Installation per NEC® 300.22(C ).
Specifications & dimensions subject to change without notice. Consult your Eaton Representative for availability and ordering in
formation.
PS519146EN
February 11, 2019 10:09 AM