Selectable special functions MM..C-503-00
Startup of Standard Design
Special function 3
MOVIMOT
®
with adjustable current limitation (switchable via terminal f1/f2), with
reduction of frequency if exceeded
Function descrip-
tion
The current limitation can be set via switch f2. The binary input terminal f1/f2 can be
used to toggle between maximum current limit and the current limitation set via switch f2.
Response after
reaching the cur-
rent limitation
After reaching the current limit, the unit reduces the frequency using the current lim-
itation function and if necessary stops the ramp to prevent the current from increas-
ing.
If the unit operates at the current limitation, the status is displayed through rapid
green flashing of the status LED.
In-system values
for setpoint f2/mini-
mum frequency
It is no longer possible to toggle via terminals between setpoint f1 and setpoint f2 in
terminal operation or to set the minimum frequency in bus operation.
The minimum frequency in bus operation is fixed at 2 Hz.
Adjustable current
limits
Selection of cur-
rent limits via
binary input termi-
nal f1/f2
05598AXX
1
6
7
85
4
3
2
ON
S2
6
7
85
3
4
5
6
7
8
Switch f2
Detent position 012345678910
I
max
[%] of I
N
60 70 80 90 100 110 120 130 140 150 160
03819AXX
f1/f2 = "0" 160 % current limitation is active
03820AXX
f1/f2 = "1" The current limitation set via switch f2 is active.
The selection can also be made with enabled unit.