Operating Instructions – MOVIMOT® MM03C - MM3XC
59
7
Selectable special functions MM..C-503-00
Startup of Standard Design
Special function 1
MOVIMOT
®
with increased ramp times
Function descrip-
tion
It is possible to set ramp times up to 40 s.
If 3 process data words are used in bus operation, a ramp time of up to 40 s can be
transmitted.
Changed ramp
times
Special function 2
MOVIMOT
®
with adjustable current limitation (fault if exceeded)
Function descrip-
tion
The current limit can be set via switch f2.
The setpoint f2 (with control via terminals) or the minimum frequency (with control via
RS-485) can no longer be changed and is fixed at the following values:
Setpoint f2: 5 Hz
Minimum frequency: 2 Hz
Monitoring becomes effective above 15 Hz. If the drive is operated at the current limit
for more than 500 ms, the unit changes to the fault status (fault 44). The status is in-
dicated through rapid red flashing.
Adjustable current
limits
05592AXX
1
6
7
85
4
3
2
ON
S2
6
7
85
Switch t1
Detent position 0123456 7 8 9 10
Ramp time t1 [s] 0.1 0.2 0.3 0.5 0.7 1
20 25 30 35 40
= Corresponds to standard setting
= Changed ramp times
3
4
5
6
7
8
05596AXX
1
6
7
85
4
3
2
ON
S2
6
7
85
3
4
5
6
7
8
Switch f2
Detent position 012345678910
I
max
[%] of I
N
90 95 100 105 110 115 120 130 140 150 160
00
I