57
7
Description of the DIP switches S2
Startup of Standard Design
DIP switches
S2/3
Control process
• DIP switches S2/3 = OFF: VFC operation for 4-pole motors
• DIP switches S2/3 = ON: U/f operation reserved for special cases
DIP switches
S2/4
Speed monitoring
• Speed monitoring (S2/4 = "ON" is used for the protection of the drive during blocking.
• If the drive is operated at the current limit for more than 1 second with active speed
monitoring (S2/4 = "ON"), the speed monitoring trips. MOVIMOT
®
signals a fault via
status LED (red, flashing slowly, fault code 08). The current limit must be attained un-
interruptedly for the duration of the delay time before the monitoring function re-
sponds.
DIP switches
S2/5 to S2/8
Selection of options
• Special functions can be selected using the binary coding of the DIP switches.
• The possible values can be set as follows:
• An overview of the selectable special functions can be found on page 58.
Decimal
Value
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
S2/5 –
X – X – X – X – X – X – X – X
S2/6 ––
X X ––X X ––X X ––X X
S2/7 ––––
X X X X ––––X X X X
S2/8 ––––––––
X X X X X X X X
X = ON
–= OFF