Important startup instructions
Startup of Standard Design
7 Startup of Standard Design
7.1 Important startup instructions
It is essential to comply with the safety notes during installation!
Before removing/attaching the MOVIMOT
®
inverter, it must be disconnected
from the power supply system (mains). Dangerous voltages may still be
present for up to 1 minute after shutdown.
Ensure before startup that the drive has not been damaged.
Check that all protective covers are installed correctly.
Use "CW/Stop" or "CCW/Stop" for jog mode.
A minimum switch-off time of 2 seconds must be maintained for the mains contactor
K11.
7.2 Description of the controls
Setpoint potenti-
ometer f1
The potentiometer has a different function, depending on the unit operating mode:
Control via terminals: Setpoint f1 (selected by tl. f1/f2 = "0")
Control via RS-485: Maximum frequency f
max
Setpoint switch f2
The function of the switch changes depending on the unit operating mode:
Control via terminals: Setpoint f2 (selected by tl. f1/f2 = "1")
Control via RS-485: Minimum frequency f
min
Switch t1
For integrator ramp (ramp times based on a setpoint jump of 50 Hz)
05066BXX
[1] Pot. position
123456789100
100
f [Hz
[1]
]
2
75
25
50
6
5
f
1
Switch f2
Detent position 0 12345678910
Setpoint f2 [Hz] 5 7 1015202535506070100
Mini. frequency [Hz] 2 5 7 10 12 15 20 25 30 35 40
3
4
5
6
7
8
Switch t1
Detent position 012345 678910
Ramp time t1 [s] 0.1 0.2 0.3 0.5 0.7 1 235710