Manual

30
Operating Instructions – MOVIMOT® MM03C - MM3XC
5
Connection MOVIMOT® options
Electrical Installation of MOVIMOT® Standard Design
Connection of
URM option
The following figure shows the connection of the URM option.
Connection of
MDG11A option
The following figure shows the connection of the MDG11A option.
The diagnostic unit must be connected prior to the possible occurrence of a fault, as
MOVIMOT
®
error messages are not saved and the information is lost when the 24 V
supply is disconnected.
Connecting the MDG11A to an RS-485 bus with several MOVIMOT
®
is not al-
lowed.
The diagnostic unit can be used if the MOVIMOT
®
is controlled via terminals
(= address 0 [S1/1-S1/4 = OFF]).
Do nut use the diagnostic unit if setpoint setting takes place via the RS-485 in-
terface.
52203AXX
M
3~
13
RD
14
15
24V
R
L
f1/f2
K1a
K1b
RS-
RS+
BMG
URM
13
14
15
WH
BU
L1
L2
L3
MOVIMOT
®
03404CXX
[1] EMC metal cable gland
For operation see the section "Diagnostics"
MDG11A
24V
RS+
RS-
13
14
15
L1
L2
L3
24V
R
L
f1/f2
K1a
K1b
RS-
RS+
MOVIMOT
®
[1]