Operating Instructions – MOVIMOT® MM03C - MM3XC
117
9
Startup procedure
Startup with Communications Interface / Fieldbus
9 Startup with Communications Interface / Fieldbus
9.1 Startup procedure
1. Review correct connection of MOVIMOT
®
(see the section "Electrical Installa-
tion").
2. Set the correct RS-485 address on DIP switches S1/1...S1/4. Always set address
"1" in conjunction with SEW fieldbus interfaces (MF...).
3. Set the minimum frequency f
min
with switch f2.
4. If ramp is not set via fieldbus, set ramp time with switch t1 (ramp times are based on
a setpoint jump of 50 Hz).
5. Check whether the required direction of rotation is enabled.
Decimal
address
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
S1/1 – X – X – X – X – X – X – X – X
S1/2 ––
X X ––X X ––X X ––X X
S1/3 ––––
X X X X ––––X X X X
S1/4 ––––––––
X X X X X X X X
X = ON
–= OFF
Switch f2
Detent position 012345678910
Minimum frequency f
min
[Hz]
2 5 7 1012152025303540
Switch t1
Detent position 012345678910
Ramp time t1 [s] 0.10.20.30.50.71235710
Terminal R Terminal L Message
Activated Activated • Both directions of rotation are enabled
Activated Not activated • Only clockwise direction of rotation is enabled
• Preselected setpoints for counterclockwise rotation result in
standstill of drive
Not activated Activated • Only counterclockwise direction of rotation is enabled
• Setpoint selections for clockwise lead to the drive being
stopped
Not activated Not activated • Unit is blocked or the drive is stopped
3
4
5
6
7
8
3
4
5
6
7
8
24V
R
L
24V
R
L
24V
R
L
24V
R
L
00
I