Startup procedure
Startup with Communications Interface / Fieldbus
9 Startup with Communications Interface / Fieldbus
9.1 Startup procedure
1. Review correct connection of MOVIMOT
®
(see the section "Electrical Installa-
tion").
2. Set the correct RS-485 address on DIP switches S1/1...S1/4. Always set address
"1" in conjunction with SEW fieldbus interfaces (MF...).
3. Set the minimum frequency f
min
with switch f2.
4. If ramp is not set via fieldbus, set ramp time with switch t1 (ramp times are based on
a setpoint jump of 50 Hz).
5. Check whether the required direction of rotation is enabled.
Decimal
address
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
S1/1 X X X X X X X X
S1/2 ––
X X ––X X ––X X ––X X
S1/3 ––––
X X X X ––––X X X X
S1/4 ––––––––
X X X X X X X X
X = ON
–= OFF
Switch f2
Detent position 012345678910
Minimum frequency f
min
[Hz]
2 5 7 1012152025303540
Switch t1
Detent position 012345678910
Ramp time t1 [s] 0.10.20.30.50.71235710
Terminal R Terminal L Message
Activated Activated Both directions of rotation are enabled
Activated Not activated Only clockwise direction of rotation is enabled
Preselected setpoints for counterclockwise rotation result in
standstill of drive
Not activated Activated Only counterclockwise direction of rotation is enabled
Setpoint selections for clockwise lead to the drive being
stopped
Not activated Not activated Unit is blocked or the drive is stopped