Product Overview

10. LIMITED WARRANTY
RectorSeal, LLC makes the Limited Express Warranty that when the instructions for storage and handling of our products are followed we warrant our products to be free from defects. THIS LIMITED
EXPRESS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PAR-
TICULAR PURPOSE, AND OF ANY OTHER OBLIGATION ON THE PART OF RECTORSEAL, LLC. The sole remedy for breach of the Limited Express Warranty shall be the refund of the purchase
price. All other liability is negated and disclaimed, and RectorSeal, LLC shall not be liable for incidental or consequential damages.
Suggestions and recommendations covering the use of our products are based on our past experience and laboratory findings. However, as we have no control as to the methods and conditions
of application, we only assume responsibility for the uniformity of our products within manufacturing tolerances.
D-17
METACAULK
®
1000
pack and in 5 gallon (18.9 L) pails.
8. Limitations
Metacaulk
®
1000 is not designed to
be used in areas under continuous
immersion or in areas which would
be continuously wet. Metacaulk
®
1000 should not be used against hot
uninsulated surfaces above 300˚ F
(149˚ C).
9. Cautions
FOR CHEMICAL EMERGENCY, SPILL,
LEAK, FIRE, EXPOSURE OR ACCIDENT,
CALL CHEMTREC-DAY OR NIGHT 1-800-
424-9300.
PRECAUTIONS: Do not take internally. May
be harmful if swallowed. May cause eye and
skin irritation if prolonged or repeated contact
occurs. Wash after handling. FIRST AID:
For any overexposure, get immediate medical
attention after first aid is given. Eyes- Flush
15 minutes with clean water. Skin-Wash with
soap and water. Inhalation-Remove to fresh
air. Ingestion-Only if conscious, give large
amounts of water and INDUCE VOMITING.
FIRE AND SPILLS: Use water fog, CO
2
, foam,
or dry chemicals. Wipe up spills to prevent
footing hazard. Clean up with scrapers and
water. STORAGE AND HANDLING: Store
away from heat sources. Keep container closed.
Do not reuse empty container. KEEP OUT OF
REACH OF CHILDREN.
For additional information, refer to Safety Data Sheet.
For additional technical service,
call: 1-800-231-3345
fax: 1-800-452-2824
www.rectorseal.com
www.metacaulk.com
with Fungal Growth Rating results of zero.
3. Applications
Metacaulk
®
1000 can be used in
interior applications as a general
purpose fire rated sealant and smoke
seal for construction joints on both
vertical and horizontal surfaces.
Metacaulk
®
1000 is also an excellent
fire rated acoustical sealant and can
be used in areas under constant
vibration or movement. Metacaulk
®
1000 can also be used on various
penetrations such as EMT, telephone
& power cables, insulated pipes, etc.
in concrete floors and walls , gypsum
walls as well as wood floors. Use
Metacaulk
®
1000 to prevent the spread
of fire and smoke through joints in fire
rated gypsum wallboard partitions,
concrete block or concrete walls and/
or concrete or corrugated steel deck
floor/ceiling assemblies.
4. Installation Data
Install Metacaulk
®
1000 using standard
caulking techniques or trowel from
pails. Metacaulk
®
1000 may also
be pumped from the pails. When
damming materials are needed,
use only materials approved for the
specific application.
TYPICAL TOP OF WALL
INSTALLATION
Step 1)
Cut and fit the gypsum wallboard to the
contour of the steel decking leaving a
maximum 3/4" (19 mm) relief gap.
Step 2)
Pack the flute openings and relief gap
with required amount of fiberglass
insulation and recess to required
depth.
Step 3)
Gun, trowel or pump the sealant
as required to the specified depth.
Properly tool sealant surface flush
with the wall.
Consult UL Directory for complete
instructions and system listings.
5. Testing Data
For specific test criteria, refer to the UL's
Fire Resistance Directory or Warnock
Hersey International Listing Directory
or call RECTORSEAL
Metacaulk
®
1000 was tested at positive
pressure with a minimum 0.01 (2.5 Pa)
inches water and in accordance with
ASTM E814 (UL 1479), UL 2079 and
ULC-S115-95.
Complies to Required Environmental
Exposure Testing of Accelerated Aging
and High Humidity as per UL 1479 Fire
Test of Through-Penetration Firestops.
FBC System Compatible indicates that this product
has been tested, and is monitored on an ongo-
ing basis, to assure its chemical compatibility with
FlowGuard Gold®, BlazeMaster® and Corzan® pipe
and fittings.
FBC, FlowGuard Gold®, BlazeMaster® and Corzan® are
licensed trademarks of the Lubrizol corporation.
6. Storage & Handling
Metacaulk
®
1000 should be stored
between 35˚F (2˚C) and 120˚ F (49˚ C). to
obtain a minimum 3 year shelf life. NOTE:
Do not dilute, no mixing is required. Best
if protected from freezing. If freezing
occurs, thaw completely before using.
Keep products stored under protective
cover in original containers.
7. Availability
Metacaulk
®
1000 is available in 10.3
oz. (304 ml), 30 oz.(887 ml) caulking
tubes and 20.2 oz. (597 ml) sausage