Product Overview
Installation Data
Install Metacaulk 150+ using standard caulking techniques or trowel from pails.
Metacaulk MC 150+ may also be pumped from the pails. When damming materials are
needed, use only materials approved for the specific application.
TYPICAL GYPSUM WALLBOARD INSTALLATION
Step 1 Cut opening in wall.
Step 2 Clean penetration opening and surfaces from loose debris, dirt, oil and wax.
Step 3 If required, install sleeve and backing material.
Step 4 Gun the sealant as required to the specified depth. Trowel surface flush with
wall.
Consult third part testing agency product listing directory for complete instructions
and system listings.
Testing Data
For specific test criteria, refer to Intertek Directory and UL Product iQ or call
RectorSeal.
Metacaulk 150+ was tested at positive pressure with a minimum 0.01 inches of water
(2.5 Pa) and in accordance with ASTM E814 (UL 1479), ASTM E1966 (UL 2079). Tested to
the time-temperature requirements of ASTM E119 (UL 263). L rating > 1 cfm cu.ft. Class
1 W-Rated.
Sound Transmission Class (STC) 65 - The test was performed in accordance with
ASTM E90, Standard Test Method for Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions and Elements.
Tested by a third party independent laboratory to the ASTM G21 standard with Fungal
Growth Rating results of zero.
FBC™ System Compatible indicates that this product has been tested, and is monitored on an on-
going basis, to assure its chemical compatibility with FlowGuard Gold®, BlazeMaster® and Corzan®
piping systems and products made with TempRite® Technology.
The FBC System Compatible Logo, FBC™, FlowGuard Gold®, BlazeMaster®, Corzan® and TempRite® are trademarks of Lubrizol
Advanced Materials, Inc. or its affiliates.
Inspection & Repair
RectorSeal recommends that a firestop system inspection be conducted during
installation of the material in accordance with ASTM E2174 and ASTM E2393. In the
event post-installation inspection and destructive sampling is necessary, RectorSeal
advises repairing the damaged firestop system by replacing any material that was
removed or damaged with the same product originally installed, and ensuring
the assembly matches the original firestop listing. RectorSeal advises, that due to
the chemical nature of firestop products and sealants, material depth should be
determined by measuring the points of adhesion at the substrate bond area as
sealants may decrease in size during the curing process.
Storage & Handling
Metacaulk 150+ should be stored between 35˚F (2˚C) and 120˚F (49˚ C) to obtain a 3 year
shelf life.
NOTE: Do not dilute, no mixing is required. Best if protected from freezing. If freezing
occurs, thaw completely before using. Keep products stored under protective cover in
original containers.
Asbestos Fillers None
Solvents None
Hazardous
Ingredients
None
Application Caulking Gun
or Towel
Application
Temperature
between
40˚F - 120˚F
4˚C - 49˚C
Color Red / Gray
Cure Time 3 to 4 weeks
(at 77˚F/25˚C)
Density 12.5 lbs/gal
Elastomeric Yes
Freeze/Thaw Excellent
Skin Over Time 30 min.
(at 77˚F/25˚C)
pH Value 7 to 8
Volume Coverage:
for 10.3 oz. tube (304 ml) 18 cu. in.
for 20.2 oz. foil packs (597 ml) 36 cu. in.
for 30 oz. tube (887 ml) 54 cu. in.
for 5 gallon (18.9 liter) 1155
cu. in.
VOC < 10 g/l
ASTM E84, UL 723 Tunnel Test
Flame Spread 10
Smoke Index 0
Material Properties