Product Overview

10. LIMITED WARRANTY
RectorSeal makes the Limited Express Warranty that at the date of delivery this product will be free from defects in RectorSeal materials and workmanship. THIS LIMITED EXPRESS WARRANTY
IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, AND
OF ANY OTHER OBLIGATION ON THE PART OF RECTORSEAL . The sole remedy for breach of the Limited Express Warranty shall be the refund of the purchase price. All other liability is negated
and disclaimed, and RectorSeal shall not be liable for incidental or consequential damages.
Suggestions and recommendations covering the use of our products are based on our past experience and laboratory findings. However, as we have no control as to the methods and conditions
of application, we only assume responsibility for the uniformity of our products within manufacturing tolerances.
G-13
Metacaulk
®
Fire Rated Putty and Putty Pads
the stud and adhere. Work
pad to the opposite side of
the box and over the edges
(Step 2). If wall membrane is
in place, pack putty into gaps
between box and gypsum
board slightly overlapping
inner wallboard surface. If
membrane is to be installed
after pad installation, overlap
front edge of box so that putty
will be compressed around
edges of box as wallboard is
installed. Cut slits in pad to
fit around conduit or cables
(Step 3). Press pad to surface
of top, bottom, and sides of
box (Step 4). Trim excess at
corners and apply to conduit
fittings connected to the box.
Remove exposed liner. Op-
tionally, putty may be packed
into inside of conduit fittings
to prevent passage of smoke.
Only one putty pad thickness
(1/8") is needed for a 1 or 2
hour rating.
5. Testing Data
Metacaulk
®
Fire Rated Putty
is classified by Underwrit-
ers Laboratories, Inc. as a
fill, void or cavity material.
Metacaulk
®
Fire Rated Putty
Pads are classified as a wall
opening protective material.
For specific test criteria see
UL Fire Resistance Directory
or call
RECTORSEAL.
Metacaulk
®
Fire Rated Put-
ty was tested at a minium
0.01 inch of water, positive
pressure in accordance with
UL 1479, ASTM E 814 and
CAN4-S115-M.
6. Storage & Handling
Metacaulk
®
Fire Rated Putty
is not to be stored in areas
where the temperatures ex-
ceed 120˚F or drop below
0˚F. Best if protected from
freezing. If freezing occurs,
thaw completely before using.
Keep products dry and stored
under protective cover in their
original containers. Products
have a minimum shelf life of 2
years subject to re-inspection
thereafter. A stock rotation
program is recommended.
7. Availability
Moldable Fire Rated Putty
available in 1 1/2 inches di-
ameter by 10 inches long (18
cubic inches)
Moldable putty pads are 6
inches by 7 inches by 1/8 inch
thick.
8. Limitations
Do not expose to water.
9. CAUTIONS
FOR CHEMICAL EMER-
GENCY, SPILL, LEAK, FIRE,
EXPOSURE OR ACCIDENT,
CALL CHEMTREC - DAY OR
NIGHT 1-800- 424-9300.
For additional information,
refer to Material Safety Data
Sheet
For additional technical
service,
call: 1-800-231-3345
Fax: 1-800-452-2824
RECTORSEAL
2601 Spenwick Drive Houston, Texas 77055
www.rectorseal.com
www.metacaulk.com