Product Overview

PRODUCT DATA SHEET
METACAULK
®
COVER GUARD™
Fire-rated gasket for electrical boxes
December 2017
be used as a solution for stan-
dard electrical boxes when the
100 square inch rule is violated.
Metacaulk
®
COVER GUARD
is UL tested and can be used
with both metal and plastic cover
plates. Tested conditions for one
and two hours.
4. Installation
Instructions
Metacaulk
®
COVER GUARD
is
easy to install. 1) Place aluminum
foil side of Metacaulk
®
COVER
GUARD
against inside of elec-
trical face plate. 2) Do not re-
move any material, film or foil from
Metacaulk
®
COVER GUARD
. 3)
Install face plate with Metacaulk
®
COVER GUARD
over switch or
receptacle and secure face plate
with screws.
2. Material Properties
Asbestos Fillers None
Solvents None
Hazardous Ingredients None
Sizes :
66276 Single switch
66274 Double switch
66272 Single receptacle
66270 Double receptacle
66265 Single Decor
66266 Double Decor
Packed 50 per case
Color Black
ASTM E 84, UL 723 Tunnel Test
Flame Spread 5
Smoke Index 5
Sound Transmission Class
STC Rating 54*
*Tested in a UL 411 wall assembly/section to ASTM E90
3. Applications
Metacaulk
®
COVER GUARD
is
used when electrical boxes are
installed in rated walls facing op-
posite directions and horizontally
separated by less than 24". Meta-
caulk
®
COVER GUARD
can also
1. Product Description
Metacaulk
®
COVER GUARD
is
a single component fire rated
gasket for use with electrical
boxes when addressing the
"24 inch rule". It is mounted on
the inside of the cover plate
and installed at the same time
as the cover plate, covering
the opening and providing the
necessary fire protection. When
exposed to heat, Metacaulk
®
COVER GUARD
's highly in-
tumescent nature causes it to
expand forming a char that
will seal off the opening and
prevent the spread of flames
and limit the temperature rise
on the unexposed surfaces.
Metacaulk
®
COVER GUARD
is applied by hand, does not
take up volume in the electri-
cal box and is a labor saving
replacement for putty pads in
normal applications. U.S. Pat-
ent No. 6,207,085; 6,252,167 &
7,348,484.
Metacaulk
®
COVER GUARD
Features
* Easy to Install
* Cost Effective
* Great for safe retrofit applica-
tions
* Reduces sound transmission
For list of systems see metacaulk.com.