Specifications

Archimod®
Operating and maintenance manual
67
MESSAGE MEANING
First start-up:
connect the mains!
The UPS has never been switched on. No mains supply.
Start-up not allowed.
Make sure the mains are present before starting up.
No mains! start-up not allowed
No mains supply. Start-up not allowed.
To start the UPS on battery, select this conguration via the display.
Emergency Power Off!
The Emergency Power O (EPO) is working, the EPO command has been given
by a push button or a disconnecting switch on the input line was opened while
the UPS was working.
Config. incomplete for start-up!
The UPS requires a complete start-up conguration.
Ensure that the output conguration, bypass enable, KB number, number of
batteries for KB and the output voltage have been entered correctly.
Three-phase circuit sequence
incorrect!
Invalid three-phase input sequence.
Check that the three-phase circuit has been connected correctly.
The pms’ hw versions are incorrect
One or more Power Modules are not compatible with the UPS.
Call assistance.
Start-up error! An error occurred during start-up of the UPS.
Start-up interrupted
Start-up possible only by conrming.
Start-up was not conrmed within 30 seconds.
UPS shut down by programming! UPS shut down by programming.
Shutting down due
to an incorrect configuration
An error occurred in conguration. UPS in shutting down.
The number of Power Modules detected by the UPS is incorrect
for the output conguration set.
Shutting down due to a wrong
KBnumber
An error occurred when conguring the KBs.
Set the right KB number
Shutting down due
to end of autonomy
Battery charge level is too low, UPS in shutting down.
Maximum time on battery
The UPS has been running on battery for the maximum time set,
UPS shutting down.
Load not fed. Load feeding interrupted.
Feeding from the output
Error in starting up. Voltage present on the UPS output.
Check connections.
Shutting down with H.V. buses
loaded
The UPS did not shutdown correctly.
Make sure the DC buses are discharged prior to carrying out any maintenance
on the unit.
Current data saving error Error in saving some of the UPS parameters.
The CMs SW releases
are not correct: Update them!
The commands are programmed with dierent SW releases.
The software releases need aligning.
Start the UPS in the Service mode and align the commands’ Software.
FRAMES DISPLAYED WHEN SHUTTING DOWN