7.2.4 Events
Events
Visual display
All Displays all the events
Critical
Displays events that have generated
critical alarms
Malfunctions
Displays events that have generated
non critical alarms
Info
Displays events that have generated
simple information
Deletion All Deletes all the events
7.2.5 Tools
Batteries
Battery test Tests the batteries to check their condition and performance.
Batt. Calibration
Calibrates the batteries, measuring the run down curve.
If the battery is changed, we recommend carrying out this cycle so that
the UPS provides precise information about the charge status.
Battery cycle
Executes a Battery Test and battery equalisation to verify their status
and performance and to maximise battery life.
Signalling
Test (*)
Tests the luminous signals. Press “ENTER” to carry out the test on the signals
of the status indicator (green, orange and red) and the acoustic signals
LCD Display
Test(*)
Tests the alphanumerical display.
By pressing “ENTER” all the characters available on the alphanumerical display are shown.
(*) Available in the “Service Mode” only
Assistance
Displaying the ID Displays the code to communicate to assistance if a request is made.
Using code Enter the code given by technical assistance.
Reset CM Errors Deleting the memory of errors detected by the command. It resets only resettable errors.