Specifications

58
®
7. Control panel
(*) Disponibile solo in “Service Mode”
ATTENTION
Set the total KB value and Capacity correctly for the batteries being used. If set incorrectly there is the danger of
damaging the batteries.
Batteries
Threshold Values
Aut end warning
Setting the start time of the end of battery
autonomy warning
Max. Battery time
Setting the maximum time of the UPS
running on battery [sec].
When this battery time is up the UPS shuts
down.
Set OFF to disable to function.
Battery Charger Charge in Standby
If enabled, it enables battery charging with
the UPS off.
Restart
Restart Enabling
Enables or disables restarting of the unit
when mains power returns after
the batteries have run down completely
Minimum autonomy
Minimum percentage of autonomy
for restarting
Total KBs
Sets the total number of KBs installed (1 KB = 3 battery boxes)
Necessary for the UPS to supply correct autonomy values on the basis
of the load applied and for correct battery charging.
Capacity (*) Sets the capacity value of the batteries in the UPS [Ah]
Operator
Panel
Language Sets the display language
Buzzer Enables/disables all acoustic signals
Keyboard Beep Enables/disables the acoustic signalling when the keys are pressed
Shutting down block (*) If enabled a password is required to shut the UPS down
Display Backlighting
Sets display backlighting
- Fixed: always lit
- Timed: lighting turns off if the keyboard is not used for 1 minute
- Disables: lighting always off
Display Contrast Sets display contrast
Password change Sets a password that prevents access to UPS settings
Password level The default setting is in the USER item
(*) Only available with the password chosen