Specifications

50
®
7. Control panel
7.1 “Service Mode” function
This is the mode in which the Archimod® UPS is to be used when setting up during installation and for managing software
upgrades of commands and Power Modules.
To access this mode press “ENTER” with the UPS off; the display turns on and the navigation MENU can be surfed. One of
the seven languages available can be chosen for the strings displayed: Italian, English, German, French, Russian, Spanish
and Polish.
To exit this mode press the “ON/OFF” key otherwise, after 20 minutes without receiving any manual or serial commands,
the UPS exits the function automatically and shuts down.
7.2 Main menu and Submenus
Press the ON/OFF button to start the UPS and confirm with the ENTER key when prompted.
At the end of the start-up procedure the main frame appears on the display. Remember that when starting the voltage in
output from the machine is present only when the UPS STARTUP bar reaches the end and the main frame appears.
The UP ARROW and DOWN ARROW buttons can be used to scroll the main frame pages, each one giving different
information on UPS status.
Below is a list of the main pages:
1. input – output – battery;
2. input – percentage output – battery;
3. bypass – output – battery;
4. bypass – percentage output – battery;
5. load available in output;
6. measurements on the output;
7. output line voltages;
8. measurements on the input;
9. bypass line voltages;
10. battery status.