Specifications

Archimod®
Operating and maintenance manual
17
3 104 51
3 104 52
3 104 53 3 104 54 3 104 55 3 104 56 3 104 57
Command board 1 2 3
Redundacy of command board No Yes
Percentage of load admitted
after rupture of a control board
- 50% 66% (50÷75)% (60÷80)% 66%
Model 20 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
Power Module PM7
3 PM7
driven
by control
board N.1
3 PM7
driven
by control
board N.1
3 PM7
driven
by control
board N.1
6 PM7
driven
by control
board N.1
6 PM7
driven
by control
board N.1
6 PM7
driven
by control
board N.1
3 PM7
driven
by control
board N.2
3 PM7
driven
by control
board N.2
6 PM7
driven
by control
board N.2
6 PM7
driven
by control
board N.2
3 PM7
driven
by control
board N.2
3 PM7
driven
by control
board N.3
3 PM7
driven
by control
board N.3
3 PM7
driven
by control
board N.3
6 PM7
driven
by control
board N.3
Maximum output power during
replacement mode Hot
swappable modules
- 50% 66% (50÷75)% (60÷80)% 66%
Maximum output power in case of
failure of a module (Redundancy)
0% (with
3 fhase
load)
50% 66% 75% 80% 84%
66% (with
single
fhase load)
Power Module PM7 3 6 9 12 15 18
Characteristics
of Power Module PM7
Nominale Power 6.7kVA
Active Power 5.4kW
Hot swappable electronics is permitted by dedicated procedure,
replacing a power module with the machine on after turning off,
via the relative control board, its corresponding 3-phase block
(3 or 6 power modules).
Number of Display 1 2 3
Characteristics of Display
NON Hot
Swappable
Redundant.
Independent displays each connected
with a separate command.
Display back light green background
Multicolor Status Indicator operation (green / yellow / red)
RS232 user port
N.1
Rear side
N.2
Rear side
N.3
Rear side
RS232 maintenance port
N.1
Front side
N.2
Front side
N.3
Front side
Contact port
N.1 DB15
rear side
N.2 DB15
rear side
N.3 DB15
rear side
Functional electrical characteristics