Specifications
16
®
3. Technical description
3 104 51
3 104 52
3 104 53 3 104 54 3 104 55 3 104 56 3 104 57
Rated Power 20 kVA 40 kVA 60 kVA 80 kVA 100 kVA 100 kVA
Active Power 16 kW 32 kW 48 kW 64 kW 80 kW 96 kW
Technology On Line, double conversion VFI – SS - 111
Configuration I/O
Triphase / Triphase (Only Archimod 20/40kVA can be configured single/single,
single/tri, tri/single, tri/tri by user)
UPS architecture
Modular with 6,7 kVA power modules (PF = 0,8). Housed in a single cabinet.
Expendable, redundant N+X (except for Archimod 120kVA).
3 104 51
3 104 52
3 104 53 3 104 54 3 104 55 3 104 56 3 104 57
Maximum current (tri/tri) 37 A 74 A 111 A 148 A 185 A 222 A
Maximum current (tri/single) 37 A 74 A - - - -
Maximum current (single/tri) 111 A 222 A - - - -
Maximum current (single/single) 111 A 222 A - - - -
Input nominal voltage
Vac = 400V (Trifase + N) + 15% - 20%
(Only Archimod 20/40kVA Vac = 230 V +15% -20% with input single-phase)
Input frequency 50 Hz / 60 Hz ± 2%
Input connections Tri + Neutral
THD input current < 3%
Input power factor > 0.99
3 104 51
3 104 52
3 104 53 3 104 54 3 104 55 3 104 56 3 104 57
Maximum current (tri/tri) 29 A 58 A 87 A 116 A 145 A 174 A
Maximum current (tri/single) 87 A 174 A - - - -
Maximum current (single/tri) 29 A 58 A - - - -
Maximum current (single/single) 87 A 174 - - - -
Output nominal voltage
Vac = 400V ± 1% (Only Archimod 20/40kVA Vac = 230 V ± 1% with output
single-phase)
Output nominal frequency Hz = 50/60 sincronized
Output connections Trifase + Neutro
Efficiency
- Mains (On Line)
- Mains (Eco mode)
95%
99%
Over load 125% for 10 min - 150% for 1 min
Factor crest 3,5:1
General charateristics
Input characteristics
Output characteristics
3.4 Technical specifications