Specifications

49
MODELS WHAD 2000ext WHAD 2500ext
GENERAL SPECIFICATIONS
Rated/Active power 2000 VA / 1400 W 2500 VA / 1750 W
Technology On line Double Conversion VFI-SS-111
Waveform Sinusoidal
INPUT SPECIFICATIONS
Input voltage 230 V
Input frequency 50-60 Hz ±2% Autosensing
Input voltage range 184 V to 265 V at 100% of the load
Input power factor 3%
THD Input voltage range >0.99
OUTPUT SPECIFICATIONS
Output voltage 230V ± 1%
Output frequency (rated) 50/60 Hz synchronized
Crest factor 3,5 : 1
THD Output voltage 1%
Permissible overload 300% for 1 sec, 200% for 5 sec, 150% for 30 sec
Bypass Electromechanical synchronized internal automatic (for overloads and operating faults)
BATTERIES
Autonomy expansion Yes
Type/Voltage set of batteries VRLA - AGM 36Vdc
50% load autonomy 22 min 16 min
80% load autonomy 10 min 8 min
COMMUNICATION & MANAGEMENT
Display and Indicators Multicoloured LED status indicator, alarms and acoustic signals
Communication ports 1 RS232 serial port, 1 port with logic levels
Remote management
UPS Communicator software can be downloaded free of charge
from www.metasystemenergy.com web site
PHYSICAL SPECIFICATIONS
Dimensions H x L x W 460 mm x 160 mm x 425 mm
Battery cabinet dimensions H x L x W 319 mm x 160 mm x 402 mm 319 mm x 160 mm x 402 mm
Net weight 23 Kg 23 Kg
ENVIRONMENTAL CONDITIONS
Operating temperature/humidity 0 ÷ 40 °C / 20-80%
Maximum noise audible 1 m from unit < 42 dBA
Thermal dissipation 380 BTU/h 478 BTU/h
CONFORMITY
Certifications EN/IEC 62040-1-1, EN/IEC 62040-2, EN/IEC 62040-3
Standard Warranty 2 years, batteries included