Specifications
4
In order to select the right UPS according to the customer’s needs, it is mandatory to carefully evaluate the application to be protected.
Each kind of UPS de nitely has speci c features , depending on the application it has been designed for.
Knowing the power absorbed by the load is not all.
Even though the UPS has enough power to support the e ective load it doesn’t mean that’s the best choice.
CLASSIFICATION
XXX YY ZZZ
Output dependence on the Input line Output wave shape Dynamic performance on the Output
Standard EN 62040-3 de nes UPS classi cation according to the performances.
The rst part of the classi cation de nes the type of UPS:
• VFI (Voltage and Frequency Independent):
Output Voltage and Frequency are independent from the input ones (from mains). Frequency variations are controlled accordingly with
standard IEC EN 61000-2-2.
• VFD (Voltage and Frequency Dependent):
The output Voltage and Frequency are the same as the input ones with no corrections.
• VI (Voltage Independent):
The output Frequency is the same as the input ones; input Voltage variation are reduced and stabilized by electronic/passive regulating
devices.
The second part of the classi cation code de nes the output wave form during normal and battery powered operation:
• S: sinewave (THDu < 8%)
• X: sinewave with a linear load; no-sinewave with a distorting load (THDu > 8%)
• Y: no-sinewave
The third part of the classi cation code de nes the dynamic performance of the output voltage during load variations, in
three di erent conditions:
• variation of the operating modes (normal and battery-powered),
• linear load connection by steps in the normal and battery-powered modes,
• non-linear load connection by steps in the normal and battery-powered modes.
EXAMPLE
VFI SS 111
VI XX 112
VFD YY 113
BUYING GUIDE
CHOOSING THE RIGHT UPS
You can download the UPS Con gurator free of charge from our website: www.metasystemenergy.com.
It will help you determine the right size of UPS based on your needs. The modular structure of MetaSystem UPS
gives you the option of a wide choice of di erent runtimes. We have listed the most common runtimes in our
table: for any other runtimes, we suggest using the UPS Con gurator software.