UPS Uninterruptible Power Supply
UPS MetaSystem Energy 2 Latest generation UPS services Energy respectful for the environment Available in versions with power from 0.5 to 120 kVA, MetaSystem Energy UPS are characterised by high innovation and reliability, result of over 20 active patents, and hundreds of Megawatts installed each year. Designed with double conversion on-line technology capable of offering reliable power voltage without line disturbance, MetaSystem Energy UPS ensure high performance also for lower voltage models.
BUYING GUIDE CHOOSING THE RIGHT UPS In order to select the right UPS according to the customer’s needs, it is mandatory to carefully evaluate the application to be protected. Each kind of UPS definitely has specific features , depending on the application it has been designed for. Knowing the power absorbed by the load is not all. Even though the UPS has enough power to support the effective load it doesn’t mean that’s the best choice.
BUYING GUIDE SYSTEM ARCHITECTURE DISTRIBUTED ARCHITECTURE Distributed architecture is used when the application to UPS protect is not particularly critical and when there are logistic problems (e.g.: several rooms, already existing system, etc.).
BUYING GUIDE OPERATING COSTS The purchase price of a conventional UPS is generally 10-15 percent less than that of an advanced modular system. However, the purchase price is not the only decisive factor if the overall costs are considered. A conventional UPS involves higher operating costs than a system based on modular technology, which is also able to reduce the cost for wasted energy.
ENERGY COSTS One 30 kVA Trimod UPS unit Two 20 kVA conventional UPS units Load powered 16 kW Trimod 1 UPS type 24 kW Tot. 24 kW Redundancy level N+1 Efficiency of the System = 0,93 In Power 17,20 kW Out power 16 kW Efficiency delta UPS Load used 1,20 kW Load powered 16 kW Tot.
BUYING GUIDE OPERATING COSTS BATTERY MANAGEMENT The cost of battery management is an important part of the total operating costs. The batteries must always be kept in an efficient condition and must suit the load that’s being protected, so as to guarantee the performance of the UPS. TRIMOD UPS are equipped with a Smart Battery Management System improving considerably the life of the batteries, thus reducing the operating costs as well as the disposal of exhaust batteries.
COST OF SCALABILITY If a conventional system needs to be expanded, an identical UPS must be installed alongside the existing one. This needs a lot of space as well as modifications to the electrical system and wiring. Moreover, to carry out all this, the old UPS must be turned off. TRIMOD modular systems are scalabled by installing an additional power module without disconnecting the load, with no extra space required and with no further installation costs.
DK DAKER Niky Plus 10 DHEA POWER STATION Whad Rack Whad SINGLE PHASE ONLINE VFI MegaLine Rack MegaLine MODULAR SINGLE PHASE ONLINE VFI TRIMOD ARCHITRIMOD MODULAR THREE PHASE VFI 3.500 3.000 2.500 2.250 2.000 1.750 1.500 1.250 1.
5 10 20 40 60 120 5 10 20 40 60 120 5 10 20 40 60 120 5 10 20 40 60 120 5 10 20 40 60 120 5 10 20 40 60 120 5 10 20 40 60 120 5 10 20 40 60 120 5 10 20 40 60 120 11 Runtime (min) 120.000 100.000 80.000 60.000 45.000 30.000 20.000 18.000 16.000 14.000 12.000 10.000 9.000 8.000 7.000 6.000 5.000 4.500 4.
MODULAR THREE PHASE VFI The three-phase UPS range developed and produced by Metasystem Energy is unique in its field, and only consists of Modular UPS. The UPS system is essential for the protection of critical environments such as data centres and industrial or emergency applications from unwanted power cuts, and from damage to the equipment caused by the power supply.
possible to configure the input and the output both as one-phase and three-phase, with the possibility of obtaining all the different combinations. One-phase/One-phase, Three-phase/One-phase, Three-phase/Three-phase, and One-phase/Threephase. The range includes solutions from 8 kVA up to 120 kVA.
EXCLUSIVE FEATURES 14 Simple installation Quick maintenance The maximum transportation and installation simplicity is ensured by the reduced weights and sizes of the system modules. One person can very easily transport an three-phase UPS using a commercial vehicle, move it to the inside of the building, and install it in total safety.
SMART BATTERY CHARGER system Reduced consumption The 3-stage intelligent charger system, “Smart Charger”, prolongs battery life considerably even by 50%, halving the number of replacements and environmental pollution linked to battery disposal. Because the impact on electric consumption of an UPS system is rather relevant, when choosing a new one it is important to take into account quality and energy efficiency considerations, which can bring reductions in power consumption.
MODULARITY= SCALABILITY POWER 30 kVA LOAD 30 kVA POWER 60 kVA LOAD 60 kVA Scalability FLEXIBILITY ACROSS TIME In order to expand a traditional system, another similar UPS can be added to the existing one. This requires more space, as well as modifications to the electric system and the wiring. With modular systems, the updating is performed by installing an additional power module, without any interruption of the load, or increase in size, without bringing further installation costs.
MODULARITY= REDUNDANCY NORMAL OPERATION OPERATION IN CASE OF FAULT With the correct sizing of the power modules, it is possible to split the load so that the modules do not operate at 100% of their power. If one of the modules becomes faulty, the others continue to power the load, sharing the power that previously was supplied by the faulty module.
MODULAR THREE PHASE VFI ARCHIMOD 18
ARCHIMOD® is the innovative modular and expandable architecture system that helps simplifying and speeding up the design and installation of critical medium and large size infrastructures. The system enables optimizing the size of the whole infrastructure and the management costs, reducing power consumption and the “Total Cost of Ownership”.
ARCHIMOD PROTECTING THE POWER SUPPLY 20
TUNNEL The control or power tunnel can house up to 3 power modules or additional battery charger modules, it occupies 6 U racks and is designed for connecting to other tunnels. The power tunnel features no control logic, housing only modules. The control tunnel includes control logic, the display, keyboard, status indicator and the maintenance serial interface RS232. At the back we find: a double slot for the SNMP board, an LL port, an RS232 and 5 relay contacts.
ARCHIMOD ACCESSORIES Item code Description PTH10000 Archimod cabinet, No. 1 Tunnel with control logic, No.1 distribution module 20 kVA, No.12 battery slot PTH10010 Archimod cabinet, No. 1 Tunnel with control logic, No.1 distribution module 20 kVA , No.30 battery slot PTH10020 Archimod cabinet, No. 2 Tunnel with control logic, No.1 distribution module 60 kVA , No.24 battery slot PTH10030 Archimod cabinet, No. 3 Tunnel with control logic, No. 1 distribution module 60 kVA , No.
CONFIGURATIONS POWER: 40 KVA POWER: 20 KVA RUNTIME 80% @ LOAD: 1h RUNTIME 80% @ LOAD: 20 min POWER: 60 KVA RUNTIME 80% @ LOAD: 6 min 1 CABINET 1 TUNNEL 3 POWER MODULES 1 DISTRIBUTION MODULE 30 BATTERY MODULES 1 CABINET 2 TUNNEL 6 POWER MODULES 1 DISTRIBUTION MODULE 24 BATTERY MODULES 1 CABINET 3 TUNNEL 6 POWER MODULES 1 DISTRIBUTION MODULE 18 BATTERY MODULES POWER: 80 KVA RUNTIME 80% @ LOAD: 12 min POWER: 100 KVA RUNTIME 80% @ LOAD: 10 min POWER: 120 KVA RUNTIME 80% @ LOAD: 6 min 2 CABINET 3 TUNNE
ARCHIMOD TECHNICAL FEATURES MODEL ARCHIMOD® 20 ARCHIMOD® 40 ARCHIMOD® 60 ARCHIMOD® 80 GENERAL CHARATERISTICS Power Rating 6.7 kVA per UPS Module (20kVA per 3 Modules), cosφ 0.8 Technology On Line Double Conversion VFI-SS-111 System design Modular, scalable & redundant UPS system in one single 19 inch rack cabinet.
ARCHIMOD TECHNICAL FEATURES ARCHIMOD® 100 ARCHIMOD® 120 6.7 kVA per UPS Module (20kVA per 3 Modules), cosφ 0.8 On Line Double Conversion VFI-SS-111 Modular, scalable & redundant UPS system in one single 19 inch rack cabinet. Power and/or battery modules replacement without disconnecting the UPS 400V 3F + Neutral 50-60 Hz ±2% Autosensing 400V +15%/-20% 3F < 3% ARCHIMOD® can be set up so as to achieve synchronism between the input and output frequency even for wider frequency ranges, ±14% > 0.
MODULAR THREE PHASE VFI TRIMOD 26
TRIMOD®, is a Metasystem Energy’s unique UPS module can be programmed individually so as to with power range from 8 to 60 kVA that can obtain the required input/output configuration. adapt immediately to the changing needs of This means that three-phase or single-phase the load it protects offering more power, longer voltage values can be handled on the input and autonomy and the utmost reliability.
TRIMOD CONFIGURATIONS Model TRIMOD 8 TRIMOD 10 TRIMOD 16 TRIMOD 20 TRIMOD 30 TRIMOD 45 TRIMOD 60 Nominal Power kVA 8 10 16 20 30 45 60 Active Power kW 6,4 8 12,8 16 Runtime @ 80% load (min) Cabinet total number Net Weight (Kg) Item Code 9 1 167 PTH00840 33 1 279 PTH00850 43 1 279 PTH00860 62 2 415 PTH00870 9 1 167 PTH00880 15 1 223 PTH00890 33 1 279 PTH00900 47 2 471 PTH00910 59 2 527 PTH00920 9 1 246 PTH00930 19 2 382 PTH00940 27 2 438
TRIMOD ACCESSORIES POWER accessories Item code Three phase isolation transformer 10KVA PAT0020 Three phase isolation transformer 16KVA PAT0021 Three phase isolation transformer 20KVA PAT0022 Three phase isolation transformer 30KVA P4246D Single phase isolation transformer 10KVA P4245A Single phase isolation transformer 16KVA P4245B Single phase isolation transformer 20 KVA P4245C TRIMOD accessories 8 kVA 30 kVA Item code Power Cabinet (empty) No. 3 power slots, No. 12 battery slots.
TRIMOD TECHNICAL FEATURES MODEL TRIMOD® 8 TRIMOD® 10 TRIMOD® 16 TRIMOD® 20 2,7 kVA 3,4 kVA 2,7 kVA 3,4 kVA GENERAL CHARACTERISTICS Power Rating Technology On Line Double Conversion VFI-SS-111 System Design Modular, scalable & redundant UPS system in a single cabinet INPUT CHARACTERISTICS Input Connections 230V 1PH+N,400V 3PH +N Input Frequency 230V 1PH+N,400V 3PH +N 230V 1PH+N,400V 3PH +N 230V 1PH+N,400V 3PH +N 50-60 Hz ±2% Autosensing 400V +15%/-20% 230V +15%/-20% Input Voltage Range 4
MODEL TRIMOD® 30 TRIMOD® 45 TRIMOD® 60 GENERAL CHARACTERISTICS Power Rating 3,4 kVA 5 kVA Technology 5 kVA On Line Double Conversion VFI-SS-111 System Design Modular, scalable & redundant UPS system INPUT CHARACTERISTICS Input Connections 400V 3PH + Neutral 400V 3PH + Neutral Input Frequency 400V 3PH + Neutral 50-60 Hz ±2% Autosensing Input Voltage Range 400V +15%/-20% 400V +15%/-20% Input Current Distortion 400V +15%/-20% 3% Genset Compatibility TRIMOD® can be set up so as to achie
MODULAR SINGLE PHASE VFI MEGALINE 32
Not only do the MegaLine UPS offer all the usual 8 power boards 1250 VA each one , and 10 battery kits features of the best online double conversion in their external battery cabinet, which also provides products, they also offer top-of-the class performance space for 1 extra battery charger. Extra battery and functions. They are available in two families, with cabinets, identical to the standard one supplied, can either a single or a double cabinet. be added to extend runtime even further.
MEGALINE DIAGNOSTICS Input - Output The MegaLine’s LCD display is able to give you all the information you need to manage your UPS correctly without the need for a PC connection and the relative interface software. What’s more, all the settings you may need can be programmed using the display at the time of installation. The INPUT section and OUTPUT section submenus keep the user informed of all the sensitive data concerning the UPS operation.
MEGALINE ALARMS AND SIGNALS An acoustic signal and high-visibility flashing on the backlit front panel ensure that any alarm signal is noticed immediately.
MEGALINE SINGLE CABINET Nominal power kVA Active power kW Runtime 80% load (min.) N° Cabinet Net weight(Kg) item code MEGALINE 1250 1,25 0,875 11 1 23,5 P4201N MEGALINE 2500 2,5 1,75 11 1 34 P4202N MEGALINE 3750 3,75 2,625 11 1 43 P4203N MEGALINE 5000 5 3,5 11 1 53 P4204N Nominal power kVA Active power kW Runtime 80% load (min.
MEGALINE ACCESSORIES Model Nominal Power Active Power 50% Runtime 80% Item code Dimension L x h x p (mm) MegaLine 1250 1.250 VA 875 W 20’ 11’ P4201N 270 x 475 x 570 MegaLine 2500 2.500 VA 1.750 W 20’ 11’ P4202N 270 x 475 x 570 MegaLine 3750 3.750 VA 2.625 W 20’ 11’ P4203N 270 x 475 x 570 MegaLine 5000 5.000 VA 3.500 W 20’ 11’ P4204N 270 x 475 x 570 MegaLine 5000/2 5.000 VA 3.500 W 20’ 11’ P4205N 2x (270 x 475 x 570) MegaLine 6250/2 6.250 VA 4.
MEGALINE SINGLE CABINET MODELS MEGALINE 1250 MEGALINE 2500 MEGALINE 3750 MEGALINE 5000 GENERAL CHARACTERISTICS Apparent Power Actual Power 1250 VA 2500 VA 3750 VA 5000 VA 875 W 1750 W 2625 W 3500 W Max scalability 5000 VA Max scalability 3500 W Technology UPS architecture On line double conversion VFI-SS-11 Modular, Scalable, Redundant N+X with 1250VA power boards, housed in one cabinet INPUT Input rating 230 V Input voltage range 184 V ÷ 264 V at 100% of the load Min.
MEGALINE DOUBLE CABINET MODELS MEGALINE 5000/2 MEGALINE 6250/2 MEGALINE 7500/2 MEGALINE 8750/2 MEGALINE 10000/2 GENERAL CHARACTERISTICS Apparent Power 5000 VA 6250 VA 7500 VA 8750 VA 10000 VA Actual Power 3500 W 4375 W 5250 W 6125 W 7000 W Max scalability 10000 VA Max scalability 7000 W Technology On line double conversion VFI-SS-11 UPS architecture Modular, Scalable, Redundant N+X with 1250VA power boards, housed in one cabinet INPUT Input rating 230 V Input voltage range 184 V
MEGALINE RACK Nominal Power [VA] Active power kW Runtime @ 80% load N° Cabinet Net weight (Kg) Item code MEGALINE RACK 1250 1,25 0,875 11 1 23,5 P4482N MEGALINE RACK 2500 2,5 1,75 11 1 34 P4483N MEGALINE RACK 3750 3,75 2,625 11 1 43 P4484N MEGALINE RACK 5000 5 3,5 11 1 53 P4485N Model MegaLine Rack accessories Description Item Code PW 1250 Power upgrade PAM0027 KB MegaLine/1 Runtime extension kit for inverter cabinet PAM0018 KB MegaLine/1 Runtime extension kit f
MODEL MEGALINE Rack 1250 MEGALINE Rack 2500 MEGALINE Rack 3750 MEGALINE Rack 5000 1250 VA 2500 VA 3750 VA 5000 VA 875 W 1750 W 2625 W 3500 W SPECIFICATIONS Nominal Power Active Power Max Power Scalability 5000 VA Max Power Scalability 3500 W Technology UPS Architecture Online double conversion VFI-SS-11 Modular, Scalable, Redundant N+X with 1250 VA power boards, contained in a cabinet INPUT Input Voltage 230 V Input Voltage Range 184 V ÷ 264 V @ 100% load Minimum Operating Voltage (on
SINGLE PHASE VFI WHAD 42
UPS WHAD is the evolution of the single-phase online double conversion UPS for small and medium power applications. As Metasystem Energy’s UPS, WHAD stands out for its advanced technology and also for its attractive and pioneering design. It is available in 800 VA to 6000 VA versions. The UPS WHAD devices with on-line technology (VFI) make a double conversion of the electric current on the input (AC-DC-AC). The output remains absolutely independent of the input both for voltage and frequency value.
WHAD TOTAL PROTECTION WHAD 800XL-1000XL-1500XL WITH BACK-UP TIME EXTENDIBILITY Meta System has designed these WHAD models specifically for the protection of small computer networks, servers for telephone/ data systems, office and automation equipment. For a very competitive price these models allow a high power quality protection for low power equipment.
ALARMS AND SIGNALS An acoustic signal and high-visibility flashing on the backlit front panel ensure that any alarm signal is noticed immediately. The signals are coded into various categories based on their severity (semaphore code): GREEN & NOT FLASHING Normal Operation Normal operation, no anomaly. YELLOW & FLASHING Battery Mode Battery operation, accompanied by a slow, intermittent acoustic alarm signal, which can be silenced.
WHAD WHAD 800XL-1000XL-1500XL Nominal Power [VA] Active power kW Runtime @ 80% load N° Cabinet Net weight (Kg) Item code 0,8 0,56 17 1 12 P4HO01050 WHAD 1000XL 1 0,7 13 1 12 P4HO01080 WHAD 1500XL 1,5 1,05 8 1 12 P4HO01000 Model WHAD 800XL WHAD accessories Description Item Code Battery cabinet Extra battery cabinet 160 x 319 x 402 [mm] PAO0009 for more details on hardware and software accessories, go to pages 70-95.
MODELS WHAD 800XL WHAD 1000XL WHAD 1500XL 1000 VA / 700 W 1500 VA / 1050 W GENERAL SPECIFICATIONS Rated/Active power 800 VA / 560 W Technology On line Double Conversion VFI-SS-111 Waveform Sinusoidal INPUT SPECIFICATIONS Input voltage 230 V Input frequency 50-60 Hz ±2% Autosensing Input voltage range 184 V to 265 V at 100% of the load Input power factor >0.
WHAD WHAD 2000-2500 WITH BACK-UP TIME EXTENDIBILITY Nominal Power [VA] Active power kW Runtime @ 80% load N° Cabinet Net weight (Kg) Item code WHAD 2000ext 2 1,4 10 1 23 P43206N WHAD 2500ext 2,5 1,75 8 1 23 P43207N Model WHAD accessories Description Item Code Battery cabinet Extra battery cabinet 160 x 319 x 402 [mm] PAO0009 Splitter cable Y-cable for the battery cabinet to battery cabinet connection PAO0015 Relay interface kit Relay contacts hardware support (only for models
MODELS WHAD 2000ext WHAD 2500ext GENERAL SPECIFICATIONS Rated/Active power 2000 VA / 1400 W 2500 VA / 1750 W Technology On line Double Conversion VFI-SS-111 Waveform Sinusoidal INPUT SPECIFICATIONS Input voltage 230 V Input frequency 50-60 Hz ±2% Autosensing Input voltage range 184 V to 265 V at 100% of the load Input power factor 3% THD Input voltage range >0.
WHAD WHAD 3000-4000-5000-6000 Nominal Power [VA] active power kW Runtime @ 80% load N° Cabinet Net weight (Kg) item code WHAD 3000 3 2,1 12 1 55 P43208N WHAD 4000 4 2,8 11 1 55 P43209N WHAD 5000 5 3,5 10 1 65 P43210N WHAD 6000 6 4,3 10 1 65 P43211N Model WHAD accessories Description Relay Interface Kit Relay contacts hardware support PAM0009 BP/1 Manual bypass for Whad 3000VA / 4000VA PAM0023 BPW Manual Maintenance Bypass for Whad 5000VA / 6000VA PAO0017 for mor
MODELS WHAD 3000 WHAD 4000 WHAD 5000 WHAD 6000 GENERAL SPECIFICATIONS Rated/Active power 3000 VA / 2100 W 4000 VA / 2800 W 5000 VA / 3500 W Technology On line Double Conversion VFI-SS-111 Waveform Sinusoidal 6000 VA / 4200 W INPUT SPECIFICATIONS Input voltage 230 V Input frequency 50-60 Hz ±2% Autosensing Input voltage range 184 V to 265 V at 100% of the load Input power factor 3% Input voltage range >0.
WHAD RACK 1U - 2U 44 mm WHAD Rack 1U Rack format 581mm 483 mm Model WHAD RACK 800 WHAD RACK 1000 Nominal Power [VA] Active power kW Runtime @ 80% load Net weight (Kg) Item code 0,8 0,56 7 10 P4486N 1 0,7 11 15,5 P4487N 88 mm WHAD Rack 2U Rack format 552mm (587 con maniglie) 483 mm Model WHAD RACK 1500 Nominal Power [VA] Active power kW Runtime @ 80% load Net weight (Kg) Item code 1,5 1,05 15 20,56 P4488N For both models there is a Battery Rack 2U , for the runtime extensio
MODELS WHAD 800 Rack WHAD 1000 Rack WHAD 1500 Rack 800 VA / 560 W 1000 VA / 700 W 1500 VA / 1050 W GENERAL SPECIFICATIONS Rated/Active power Technology On line Double Conversion VFI-SS-11 Waveform Sinusoidal INPUT SPECIFICATIONS Input voltage 230 V Input frequency 50-60 Hz ±2% Autosensing Input voltage range 184 V to 265 V at 100% of the load Input power factor 3% Input voltage range >0.
POWER STATION DHEA 54
Designed loads DHEAs are online double conversion, so they are able and provided with 3 output lines - which can to support medium power to correct mains power problems, offering protection be programmed separately for back-up time for all the loads connected up to it. management based on a user-designated hierarchy.
DHEA A REVOLUTIONARY SYSTEM 450 170 The DHEA has an inverter section and battery modules (battery packs) with a stackable design and plug and play connectivity. The lead batteries contained inside the battery packs are hermetically sealed so they do not emit any gas whatsoever. As a result, they can be used in the home without any need 309 for maintenance.
Use with a gen-set IMPUT The DHEA’s design also caters for connection of its electronic section to a genset in order to considerably increase system autonomy in case of very lengthy power black outs. Gen-sets, especially low power products, typically provide power with considerable voltage fluctuation together with characteristic frequency instability.
DHEA THE POWER STATION Model DHEA 1000 Model DHEA 1500 Model BATTERY PACK N.
Specifications DHEA 1000 DHEA 1500 Technology Online double conversion (VFI) Wave form sinusoidale Nominal Power (VA) 1000 VA Active Power (W) 700 W 1500 VA 1050 W Input Voltage 230 V Input Voltage Range Minimum Operating Voltage (on mains power) Input Frequency 184 V ÷ 265 V al 100% of the load 184V with nominal load / 100V al 50% of the nominal load 50/60 Hz ± 2% (± 14% in extended range) Input Power Factor > 0.
UPS DAKER 60
ON LINE DOUBLE CONVERSION LINE INTERACTIVE VI DK UPS range is available in 1000VA, 2000VA e Line interactive technology gives a reliable 3000VA nominal power models based on Online performance at a very affordable price. Double Conversion technology and expandable in For any Small-Office Home-Office application, UPS autonomy by adding external battery cabinets.
DAKER DK DK 1000 / DK 2000 / DK 3000 ADJUSTABLE DISPLAY FOR USE IN TOWER OR RACK 1.
Model DK 1000 DK 2000 DK 3000 1000 VA 2000 VA 3000 VA 700 W 1400 W 2100 W SPECIFICATIONS Nominal Power Active Power Technology True On-line Double Conversion VFI SS 111 INPUT Input Voltage 230 V Input Voltage Range 160V÷288V Input Frequency 50Hz / 60 Hz +/- 5% Autosensing Input Power Factor > 0,99 full load OUTPUT Output Voltage 230 V +/- 1% Output Frequency 50 Hz / 60 Hz ± 1Hz Wave form Pure Sinewave THD <3% Crest Factor 3:1 BATTERIES Runtime @ 50% load [min] 20’ 20’ 16’ Run
NIKY PLUS TOP PERFORMANCE ENTRY LEVEL UPS Niky 600 Plus / 800 Plus These UPS have three IEC output sockets, a LED indicating their operating status and a port for monitoring the operation of the UPS and executing the emergency shutdown of Windows and Linux operating systems with the softwareas standard. Protection for telephone / fax / modem / LAN 1.1 Rear view.
Nominal Power [VA] Active power kW Runtime @ 80% load Net weight (Kg) Item code Niky 600 Plus 0,6 0,3 5 7 PCI0028 Niky 800 Plus 0,8 0,4 5 7,5 PCI0029 Niky 1100 Plus 1,1 0,6 5 13 PCI0030 Niky 1500 Plus 1,5 0,9 5 16 PCI0031 Model Accessories Description item code 600/800PLUS Pack of 5 multiple output extension cord PAI0012 Niky 600 Plus Niky 800 Plus Niky 1100 Plus Niky 1500 Plus Nominal Power 600 VA 800 VA 1100 VA 1500 VA Active Power 300 W 400 W 600 W 900 W
Powerstrip Eco Interactive Harviot DAKER Niky DAKER DK DHEA WHAD Rack 66 Only for “EXT” O O O Only for WHAD 3000, 4000 CB 36 CARICABATTERIE AGGIUNTIVO PL MEGALINE MEGALINE CAVO SPLITTER BATTERY CABINET per WHAD 800, 1000, 1500XL BATTERY CABINET per WHAD 2000, 2500 KIT WHAD 800, 1000, 1250, 2000, 2500 SPLITTER UPS BATTERY 48V per WHAD RACK 800-1000 UPS BATTERY 72V per WHAD RACK 1500 WHAD RACK 800-1000-1500 SPLITTER BATTERY BOX 36V 4U CONTIENE 12 BATTERIE 7,2ah BATTERY BOX 72V 2U CONTIENE 12 BATTER
O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O Only for WHAD 2000, 2500, 3000, 4000, 5000 e 6000 Only for WHAD 5000 e 6000 O O O O O O O O O O O O O O O O O O O O Only for WHAD 3000, 4000, 5000 e 6000 O O O O O O Only for WHAD 1500, 2000, 2500, 3000, 4000, 5000 e 6000 Only for WHAD 3000, 4000, 5000 e 6000 O Only for WHAD 3000, 4000, 5000 e 6000 BY-PASS UPS per WHAD 5000/6000 BYPASS MANUALE DI MANUTENZIONE DAKER DK PW 1250 ESPANSIONE DI POTENZA KIT GUIDE RACK 1U
ACCESSORIES HARDWARE TRIMOD Power module The TRIMOD® power upgrade module enables to increase power when added to the inverter cabinet. The module is available with either 2.7 kVA, 3.4 kVA or 5 kVA power ratings. Thanks to its exclusive modular architecture, the TRIMOD® is able to be upgraded either in power and runtime, in line with the actual needs of the load, by simply adding power modules or battery drawers, with great savings in the initial cost of investment.
MEGALINE PL MegaLine An 80 cm cable to connect the inverter and battery cabinet in a tower configuration. The inverter must be put on top of the battery cabinet. MEGALINE MegaLine Splitter Y-shaped cable to connect two MegaLine battery cabinets together. If configurations include more than two battery cabinets, a splitter cable must be fitted for each extra MegaLine battery cabinet (e.g. 1 inverter unit + 5 MegaLine battery cabinets = 4 splitters).
ACCESSORIES GUIDE TO UPS MANAGEMENT On its own, a UPS is unable to guarantee total protection of the data processing systems it powers. This is due to several factors, amongst which: • Batteries do not have unlimited autonomy • Unexpected load connections, such as stoves and vacuum cleaners, can cause overloads which annul the protection provided by the UPS. • Installation in unmanned areas such as EDP rooms and basements or round-the-clock operations can make alarm reception difficult or impossible.
Integration with the IP network For this type of installation, the UPS must be connected to a special network interface in which the management software is installed. The network board is then connected to the IP network. Since the UPS is directly linked to the UPS network, its management system can send e-mail and pop-up messages, shutdown and power the computer again.
ACCESSORIES Environmental monitoring There are applications which require UPS monitoring and environmental monitoring too. With CS121 / CS121 SK it is possible to monitor temperature and humidity using special sensors. Within environmental monitoring is also possible set treshold values and program relevant job to execute as sending e-mail, pop-up message, remote computer command, shutdowns, ecc.
How to choose the right product The concepts outlined on the previous pages could give rise to doubts as to which is the best system to use and in which circumstances. To establish the best solution for every sort of requirement it is enough to answer few simple questions.
ACCESSORIES CONTROL AND COMMUNICATION UPS Communicator This is Meta System’s free solution. It comprises a group of applications that continually monitor UPS operation and protect the operating systems of the computers powered by the UPS itself. The client/server structure makes it extremely flexible, efficient, simple to use and “light” when it comes to the system resources required. UPS Communicator includes the following main modules: UPS Server: server module for UPS management through the RS232 link.
UPS Supervisor Solution that’s similar to UPS Communicator but supplied on CD-Rom. It comprises the following main modules: UPSMAN: server module for UPS management through the RS232 link. This module can control numerous events (power failure, overload, bypass, internal faults, etc..) and is able to carry out lots of actions for each one (registration in the log file, transmission of pop-up messages, e-mail transmission, program execution, local and remote shutdowns, etc...), also at different times.
ACCESSORIES CONTROL AND COMMUNICATION RCCMD This software enables a computer to receive and execute, via the TCP/IP protocol, the following remote commands transmitted by the UPS management systems: • Shutdown of the operating system • Display of pop-up messages • Execution of customized programs (.COM, .EXE, .BAT, .CMD) with the relative options All the commands received are recorded in a log file.
UNMS UNMS (UPS Network Management System) is a WEB based application that can continuously monitor the status of all the UPS installed in one or more locations by means of the UPS management systems (CS121, UPS Supervisor , SNMP) and the TCP/IP protocol. All the alarm signals generated by the various different UPS are received by the monitoring station so as to achieve an immediate and thorough diagnosis of the problem and allow the technical assistance service to act urgently if needed.
ACCESSORIES CONTROL AND COMMUNICATION Network interfaces They are special network devices designed to manage UPS autonomously.
RS232 UPS CS121B or CS121B SK HTTP / java / UPSMON Execution of remote programs SNMP, SNMP Trap management E-mail transmission (SMTP) Telnet, FTP, setup / update Log File, Historical Data File SHUTDOWN / COMMANDS / MESSAGES - Unix / Linux + agent RCCMD - Windows + agent RCCMD - MAC OS X + agent RCCMD - AS/400 + agent RCCMD - Nowell Netware+ agent RCCMD - VMware + agent RCCMD 79
ACCESSORIES CONTROL AND COMMUNICATION CS121 and CS121 SK They are the “professional” version of our network interfaces.
RS232 UPS Fire-fighting systems CS121 or CS121 SK Air conditioning Smoke detectors IN relays OUT relays Configuration via Terminal RS232 Pipe-Through MODBUS over RS232 Temperature sensors Sensor Manager MODBUS over IP HTTP / java / UPSMON Execution of remote programs SNMP, SNMP Trap management E-mail transmission (SMTP) Telnet, FTP, setup / update Log File, Historical Data File SHUTDOWN / COMMANDS / MESSAGES - Unix / Linux + agent RCCMD - Windows + agent RCCMD - MAC OS X + agent RCCMD - AS/400 + agen
ACCESSORIES CONTROL AND COMMUNICATION CS121M e CS121M SK They are the “professional” version of our network interfaces. Besides including all the functions described for the “CS121B / CS121B SK” versions, they also feature the following additional functions: • 1 multifunction RS232 port • 4 digital contacts that can be independently programmed as inputs or outputs and used for integrating with alarm systems, for example NOTE: The RS485 port is used only with the MODBUS.
RS232 UPS Fire-fighting systems CS121M or CS121M SK Air conditioning Smoke detectors IN relays OUT relays MODBUS for RS485 MODBUS over IP HTTP / java / UPSMON Execution of remote programs SNMP, SNMP Trap management E-mail transmission (SMTP) Telnet, FTP, setup / update Log File, Historical Data File SHUTDOWN / COMMANDS / MESSAGES - Unix / Linux + agent RCCMD - Windows + agent RCCMD - MAC OS X + agent RCCMD - AS/400 + agent RCCMD - Nowell Netware + agent RCCMD - VMware + agent RCCMD 83
ACCESSORIES CONTROL AND COMMUNICATION SM_T_COM sensor Temperature sensor for direct connection to the COM2 of the CS121, CS121 SK and SiteSwitch 4 (only the SS4 model) interfaces. Cannot be used with SensorManager. Temperature range : -25 to +100°C (± 0.5%) Power supply voltage : 9 to 15 V DC (straight from CS121) Dimensions [L x D x H] : 70 x 70 x 27 mm Length of connecting cable : approx. 1.
Sensor Manager Manager for environmental sensors: connects to the COM2 of CS121, CS121 SK and SiteSwitch 4 (only the SS4 model) interfaces and controls up to 8 analog inputs, 4 digital inputs and 4 digital outputs. Configuration and management are created from the previously described interfaces. The “Scale Driver” and “Offset” configuration functions allow SensorManager to be used with any analog apparatus (see specifications). Includes 1 “SM_T” temperature sensor.
ACCESSORIES CONTROL AND COMMUNICATION SM_T sensor Temperature sensor for exclusive use with SensorManager. Can be connected to another “SM_T” sensor using a dedicated connector. Temperature range : 0 to 100 °C (± 1%) Power supply voltage : 9 to 24 V DC (straight from SensorManager) Dimensions [L x D x H] : 70 x 70 x 27 mm Length of connecting cable : approx. 5 m (included) Product code : PAI0021 SM_T_H sensor Combined temperature and humidity sensor for exclusive use with SensorManager.
SiteSwitch 4 This device is used to manage energy distribution, i.e. it allows to power and shutdown the devices connected to its four independent powering outputs. For example, during a power failure, a UPS can transmit a command that shuts down the least important loads (such as laser printers) so as to provide the critical systems with as much autonomy as possible. Once the mains power returns, a command that powers these loads again can be transmitted by the same UPS.
Customer Care and Guarantee Customer Care is handled directly by our dealers. Furthermore, all Metasystem Energy UPS have Our distribution network can assist you with any 24-month warranty against manufacturing defects sales or technical support you need, before or after included in the price.
whereas non modular products minimize the number of boards to repair and are easily accessible. The result is that most problems can be solved just on the first service call or simply by exchanging the failed module.
www.metasystemenergy.com MetaSystem Energy S.R.L. AD-EXMS/UPS11C/GB Edition 04/2011 Via Rodano, 1 - 42124 Reggio Emilia - ITALY Tel. +39 0522 207000 - Fax +39 0522 207005 E-mail: info@metasystemenergy.com web: www.metasystemenergy.com metasystem energy srl reserves at any time the right to modify the contents of this booklet and to comunicate, in any form and modality, the change brought to the same..