User manual

9
Summary of operations
Visual and acoustic signals in working mode
DEVICE STATUS CONDITION
OFF Normal condition 1(…. 8)
Blinking
Unacknowledged alarm 1(…. 8)
fixed lighted
Acknowledged alarm 1(…. 8)
Alarm
led
1(…. 8)
flashing (all alarm leds)
No or invalid setup parameters
OFF No or acknowledged alarms / Disabled
Buzzer
ON One or more unacknowledged alarms
Buzzer operation
BUZZER SETTING OPERATION IN ON STATUS
Continue tone
always ON
Pulse tone
0.5 sec ON / 1.5 sec OFF
Disabled
Always OFF
Output Relay operation
RELAY SETTING OPERATION
Buzzer repeater
Follows the status of the buzzer as shown in table
above, without consideration for the buzzer setting
ON if one or more alarms are in progress
Cumulative
alarm
OFF if no alarm are in progress