Owner's Manual
Table Of Contents
BROWAN COMMUNICATIONS INC. All rights reserved. 13
[8~15] Detection interval value(must be shorter
than or equal to keepalive interval)
*Note: little-endian format.
0x03
[0~5] Buzzer alarm period in seconds
0~63 seconds
[6] Enable/disable CO2 sensor
0: disable
1: enable(default)
[7] Enable/disable proximity sensor
0: disable (default)
1: enable
1 byte
0x04
Set CO2 threshold
*Note: little-endian format.
2 bytes
0x05
Set CO2 Calibration Value
(400~2000 ppm)
*Note: little-endian format.
2 bytes
Payload Content
Command content
Ex:
000C01 || 0343 || 04E803 || 059001
00 0C01 => Set keepalive interval: 0x0C -> 12 (x 5min) = 60 min (Unit:5min),
Set Detection interval 0x01-> 1 (x 5min) = 5 mins
Note: 0 means no change (Unit: 5min)
03 43 => Buzzer alarm period in 3 seconds, enable CO2 and disable proximity
sensor: 0x43
04 E803 => Set CO2 threshold: 0x03E8 -> 1000 ppm (*Note: little-endian format.)
05 9001 => Set CO2 calibration value: 0x0190 -> 400 ppm (*Note: little-endian
format.)