Operating instructions
11
WARNING
This appliance must be earthed. Failure to do
so may result in electric shock and death.
The Oven must be connected to a separate electrical supply and
installed by a qualied and approved electrician. A suitably rated
isolating switch with a 3mm contact gap on all poles should be
tted for each oven installed.
If you are in any doubt about your electrical supply,
seek the advice of a qualied electrician
EQUIPOTENTIAL
An Equipotential Earth point is provided on the rear
panel of the oven for independent Earth (GND)
connection
WARNING: HIGH LEAKAGE CURRENT Earth
connection is essential
L1
L2
Earth
Brown
Blue
Black
230V
400V
Plug Type:
Three Phase
32Amp
IEC 60309
[ EN60309]
L1+ L2+ N+ E
[L3 is not used]
Phase Loading Diagram
Plug Type:
Single Phase
32Amp
IEC 60309
[ EN60309]
L1+N+E
N
20Amp 40Amp
L1
N
N
RED BLUE
L1
N
L2
L3
viewed from
back of plug
viewed from
back of plug
L1
N
32 Amps
N
Blue
Yellow/Green
TWIN PHASE
Circuit Breakers should be rated at 20A per Phase
and be Time Delay, Motor Start Type (European Type C).
Earth Leakage Circuit:
If the oven is connected to an Earth Leakage Circuit
Breaker device, this should allow a minimum of
30 milliamps earth current without interrupting the circuit
Oven loading per phase is not equal therefore we recommend that other electrical
equipment is connected to L3+ N.
Circuit Breakers
SINGLE PHASE
Circuit Breakers should be rated at 40A per Phase
and be Time Delay, Motor Start Type (European Type C).
Phase Loading
L2
L3
16 Amps
16 Amps
Electrical Supply
Single Phase
Oven loading
Twin Phase
Oven loading
Other
Equipment
L1
Recommended Electrical Installation Guide
Brown
[L3 Not used]
230V
230V
L3
N