WARNING
This appliance must be earthed. Failure to do so may result in electric shock and death.
EC 402S (30A)
The Oven must be connected to a separate electrical supply installed by a qualified and approved electrician. A
suitably rated isolating switch with a 3mm contact gap on both poles should be fitted for each oven installed.
Establishments with standard ( Type ‘B’ ) circuit breakers are sensitive to ‘surges’ which occur on switching on
freezers, refridgerators and other catering equipment, including microwave ovens. Because of this, we strongly
recommend that a separate Type ‘C’ circuit breaker ( designed specifically for this type of equipment ) must be fitted.
An individual, suitably rated circuit breaker should be fitted for each oven installed.
If you are in any doubt about your electrical
supply, seek the advice of a qualified electrician
WARNING
SINGLE PHASE
TWIN PHASE
Twin Phase models should be connected as shown.
The Circuit Breaker should be rated at 32A (TypeC).
SINGLE PHASE
UK models are fitted with a Blue 32Amp Plug to BS4343
The Circuit Breaker should be rated at 45A (TypeC).
TWIN PHASE
ELECTRICAL SUPPLY