TS700 Intruder Alarm Control Panel OPEN _ _ ~ OPEN ~ A 1 2 B 4 5 C 7 8 9 D ENT 0 ESC _ ~ 3 6 Sett ing the Syst em Ent er your pa ss code XXXX th en lea v e th e pro tec t ed a re a. Unsetting the System Go dir e ct ly to t he ke yp ad and en ter you r p as scod e XXXX . Resetting Ent er your pa ss code XXXX f ollow ed by EN T the n 3. Te leph on e you r a lar m com pan y and follow th eir instr uct io ns.
Contents Overview Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 3 Control Panel . . . . . . . . . . . . . . . . . . . . . . . . 3 Remote Keypads and LECs . . . . . . . . . . . . . 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Specifications . . . . . . . . . . . . . . . . . . . . . . . 4 System Configuration. . . . . . . . . . . . . . . . . . 4 Change Engineer's Passcode . . . . . . . . . . 23 Configure Chime Circuits. . . . . . . . . . . . . .
TS700 Installation Manual Overview Overview Introduction The TS700 intruder alarm control system is provided for domestic and commercial intruder alarm systems conforming to BS4737: part 1: 1986. The system consists of a control panel and at least one remote keypad. Control Panel The control panel is the controlling unit for the alarm system with its own power supply and an internal battery (supplied separately) for use during a mains failure.
Overview TS700 Installation Manual ● A printer type CPA6.P (obsolete) or a standard RS232 serial printer via a Menvier Printer Adaptor (MPA/DCI) can be connected to provide a printout of the 200 log events and system parameters. ● An output module type CPA6.OM can be connected to provide an output to a set of LEDs/relays to indicate circuit activation. Each module will provide up to eight circuit indications and two modules can be "daisy chained" to provide up to sixteen outputs.
TS700 Installation Manual System Installation System Installation Cable Routing When installing cables ensure that detection, remote keypad, bell and mains cables are kept separated from each other and that panel internal wiring is clear of the main PCB. Installing The Control Panel Proceed as follows: 1. 2. Open the control panel by removing two screws from the front cover.
System Installation TS700 Installation Manual AUX +4 +3 -2 -1 PRINTER 4 5 6 7 3 2 1 Digicom Outputs Programmable @ 100mA LINE DC FLT PWR + T5 Z5 CIRCUIT 5 AUX BELL T4 Z4 CIRCUIT 4 Z6 T6 CIRCUIT 5 Z7 T7 CIRCUIT 5 Z8 T8 CIRCUIT 5 Figure 2. TS700 Main PCB Layout TRG STB TR- H/O H/O SPK AUX TAMP + + - T3 Z3 CIRCUIT 3 BATTERY FAULT LED V POWER ON 1 AMP 1 AMP T2 Z2 CIRCUIT 2 SPKR VOL NVM 6 Auxiliary 12V Auxiliary Tamper Extension loudspeaker External sounder connections Bell fuse (1A) Aux.
TS700 Installation Manual System Installation Wiring Detection Circuits All detection circuits may be wired as "End of line" (EOL) or "Double Pole" (DP). Both methods can be used on the same system. Double Pole (DP) The DP method requires the following: ● The detector alarm and tamper contacts are connected to the zone and tamper terminals respectively. ● The combined alarm and tamper loop resistance must be less than 100 Ohms. ● The maximum number of detection devices allowed in a circuit is ten.
System Installation TS700 Installation Manual Installing Remote Keypads and LECs The following types of devices may be connected to the control panel: NETLED - 4 x 7 Segment LED display. NETSTAR - 8 Character Starburst LCD display. NETARM - Remote Arming station (Power LED & programmable "Function" LED). TS700.LEC - 2 zone local expansion card. Any combination of devices can be used on the same system, providing the total number does not exceed four. 1.
TS700 Installation Manual System Installation 100m (Max.) Spare Core I/D=1 I/D=2 I/D=3 I/D=4 Remote Keypad or LEC Remote Keypad or LEC Remote Keypad or LEC Remote Keypad or LEC A B CD E Control Panel A B CD E A B CD E A B CD E A Remote B Network C D E + Power for detectors + Power for detectors + Power for detectors + Power for detectors Figure 4.
System Installation TS700 Installation Manual Installing a Plug-on Digicom 1. A digicom type DC54 or DC58 can be fitted in the base of the TS700 main panel. The unit should be fitted in accordance with the installation instructions supplied with it and connected to JP3. 2. The alarm channels for the plug-on digicom are programmed as required (page 16). It will be necessary to fit a programmed NVM in the digicom or to program it in accordance with the instructions supplied with the unit.
TS700 Installation Manual System Installation Sounder Connections The external and internal sounder can be connected to the control panel using the following connections: AUX TAMP - These terminals provide tamper protection to auxiliary devices such as power supplies, extension loudspeaker units etc. SPK+ - Extension loudspeakers may be connected between [SPK+] and [H/O-]. The minimum impedance is 16 Ohms. Up to two may be connected to the control panel.
System Installation TS700 Installation Manual Installing Output Modules Output modules (CPA6.OM) can be used to provide an output to a set of LEDs to indicate circuit activations (mimic). Output modules will normally be fitted inside the equipment they are controlling and can be positioned up to 500 metres away from the main panel. They may be fitted inside the TS700 by fitting posts and securing them to the base.
TS700 Installation Manual System Installation Programmable Outputs The TS700 has many programmable outputs which can be used to drive relays, LED’s etc. Each output can be programmed for a different function, see "Programmable Output Types" on page 17. Control Panel Outputs The control panel has four high current programmable outputs: [-1] - Set of voltage free changeover contacts rated at 1 Amp. [-2] - Switched -ve output rated at 500mA. [+3] - Switched +ve output rated at 500mA.
System Installation TS700 Installation Manual Pre Power-Up Checks Once the system is installed, but prior to powering-up give the system one final check to ensure that: 1. The wiring conforms to the requirements detailed in this manual and that all interconnections are correct (A to A, B to B etc.). 2. All system cables are kept clear of mains supply cables, telephone cables and R.F. cables. It is recommended that cable ties be used to keep cables separated. 3.
TS700 Installation Manual System Installation Factory Default Parameters Engineer's code 1234 Master User code 5678 1 2 3 4 5 6 7 8 Panel and Walk Test Courtesy Switched Detector Code Code Code Code Remote Outputs Light 12V Reset Accepte Accepte Accepte Accepte d d d d Digicom Outputs & Channels Detection Circuits System Timers Setting Modes 1 2 3 4 5 6 7 8 Fire PA Alarm Set Eng on Site Bell On Tamper Second Alarm 01: Final Exit 02: Night (access) 03-06: Night 07: Exit Ter
Programming TS700 Installation Manual Programming Engineer Menu 1 Engineers menu 1 is selected when the engineer's passcode is entered during the unset condition. The engineer may leave engineer menu 1 by pressing the [ESC] key. The system will return to the unset condition but the remote keypads will show: "ENG ON SITE". This message will be cleared the next time a valid user passcode is entered. When engineers mode is selected the monitoring of tamper circuits is disabled.
TS700 Installation Manual No Programming Type Function 00 Bell On Active when the external Bell trigger is activated. 01 Strobe Active when the Strobe trigger is activated. 02 SW12 Used to latch devices in an alarm. Active when the system is set. 03 Detector Reset Used to power devices which require power to be removed to reset them. 04 Walk Test Active when a Walk Test is in progress. 05 Alarm Active when intruder alarm is present. 06 PA Active when a PA alarm is present.
Programming TS700 Installation Manual Detection Circuits and Attributes Detection circuits 1 to 8 for the panel and 9 to 16 for the remote keypads/ LECs are programmed as follows: 1. 2. 3. 4. 5. 6. 7. Key Ensure that "Engineer Menu 1" is selected. Press 4 to select the Circuits and Attributes option. Select circuit number (01 - 16) and press [. The current circuit type will be displayed. Enter the new circuit type, using keys 0 to 9, or A, B or C (Table 3). Press [ to accept.
TS700 Installation Manual Key Programming 1 Display Acc Attribute Type 2 2AcT Double Knock - Circuits programmed with this attribute will only cause an alarm if: a) The circuit is activated twice within the Double Knock window (this time may be set in the System Timers menu). b) The circuit remains active for the whole duration of the Double Knock window. The Double Knock attribute may only be assigned to Night, 24hr and Auxiliary circuit types.
Programming TS700 Installation Manual 2 Settling Time 3 Digicom Delay 0-199 sec When the system is part-set the communication of an alarm signal to the central station may be delayed by the value set in this timer. 4 Exit Time 0-199 sec This timer sets the delay between the user initiating the exit procedure and the system (or area) actually Setting. If during the exit time an Exit Terminator circuit is activated the exit time is cancelled and the system sets immediately.
TS700 Installation Manual 6. Programming Select new setting mode by pressing: 1 for Final Exit 2 for Exit Terminator 3 7. 8. + for Timed Exit 0 to `toggle' between all three options When the display shows the required setting press [ to accept. The display will return to step 3. Repeat steps 4 to 7 for the remaining setting groups. Press ] to return to "Engineer Menu 1". When using part set codes to set areas, the first area that is set will follow the setting mode defined by that area.
Programming Key TS700 Installation Manual YES NO 0 Bell output is set for SAB 1 Disable Master User from menu 2 options 4-9 Master user has access to all options in menu 2 2 Fire Signalled when Unset/Part Set/Full Set Fire signalled only when full Set 3 24hour circuits silent when Unset 24hour circuits audible when Unset 4 Bell is instant when Part Set Bell is delayed when Part Set (30 secs) 5 Alarm output (05) cleared when system is unset Alarm output cleared when system is reset 6 Set
TS700 Installation Manual Programming Change Date The system calendar may be changed by entering the date as four digits representing the day and month e.g., 0207 is the 2nd July. 1. 2. 3. 4. Ensure that "Engineer Menu 2" is selected. Press 3 to select the Change Date option. Enter the date as four digits. Press [ to accept. ---- Enter date (day & month). 0207 Date entered 0207 (02 July).
Programming TS700 Installation Manual Print System Log A printer may be connected to produce a print-out of the last 200 system events. 1. Ensure that "Engineer Menu 2" is selected. 2. 3. 4. Press 7 to select the Print Log option. Enter the number of events to be printed. Press [ to start printing. To stop printing select the menu again and enter 000 as the number of events to be printed. --- Enter the number of events to be printed. Press ENT to start.
TS700 Installation Manual Programming AA Action Alarm (Alarm output activated) Ac** Access Passcode (User code **entered OP with the last two digits reversed) System Open (unset) AD.** Alarm Delayed (the system is part set and Or circuit ** was activated) Omits Removed Au.** Auxiliary Alarm **activated) (circuit LT n u m b e r PA.** Lid Tamper or SAB tamper PA Alarm (from circuit number **) BF Battery Fault (battery voltage below 10.5V) PF BT Bell Test Pr Power Restored CA.
Appendices TS700 Installation Manual Appendices Domestic Part-Set Application Example The TS700 control panel can be configured so that only part of the system is armed. The following example illustrates how the TS700 alarm system is configured so that it protects different areas of a three bedroom detached house. Figure 11 shows the layout of the house and position of the detection circuits and remote keypad.
TS700 Installation Manual Appendices Using the plan of the typical three bedroom house, the following part-set arrangements are required by the occupants of the house: Full Set - All circuits to be armed. Part-set Group A - Circuits 9 and 10 to be omitted. This is required for normal night setting when everyone is in the house and have retired to bed. Part-set Group B - Circuit 10 to be omitted. This is required when the occupant of bedroom 2 is away for the weekend.
Appendices P TS700 Installation Manual 1 14 CP Stores P RK 13 C 7 C P 6 Workshop Canteen 2 C C 5 3 4 P C Sales Office 11 C 12 RK P P 8 10 RK P 9 C KEY: P C RK CP Passive Infra-Red detector Magnetic Contact Remote Keypad Control Panel Figure 12. Commercial Premises The "Part-set Codes" A, B and C only affect the circuits assigned in their respective "Part-set Group'" i.e., "Part-set Code A" will set and unset the circuits assigned as "Omitted" in "Part-set Group A".
TS700 Installation Manual Appendices Programming procedure 1. First, imagine the system is fully set. When "Part-set Code A" is entered certain circuits are required to be "Omitted" whilst others remain "Armed". Create a table listing the circuits that are to be "Omitted" (O) when "Part-set Code A" is entered. The circuits that will not be omitted must therefore remain "Armed" (A). Then imagine the system is fully set again and repeat for "Part-set Codes" B and C. Circuit No.
Installation Record TS700 Installation Manual Installation Record Circuit Programming No Location Type Access D-Knock Test Omit Reset PS A PS B PSC 24hr 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 Output 1 2 3 Outputs 4 5 6 7 Panel & remotes Digicom outputs Digicom Channel System Timers Re-arms: Settling: Digi Delay: Exit Time: Entry Time: Bell Dur: Bell Delay: D-Knock: Test Time: ACPO: Setting Modes Part-set A Part-set B Full-set Part-set C System Configuration 1: Yes / No
SET CLOCK ---- ] ENGINEER MENU 1 E1 - VIEW CIRCUITS 01-H 0 RESET MASTER USER E2 - . 2 ---- ENGINEER PASSCODE 4 Full Set Part Set A Part Set B Part Set C 01-A 01-N POWER CONFIGURE 24 HR OMIT GROUP 6 7 Press ESC to stop Ln01. SYSTEM PRINT 7 PS. - CONFIGURATION con.-.. CONFIGURATION 9 Ur.0.
Menvier Security Ltd. Kenn Road, Clevedon, Bristol BS21 6LH, England Tel: +44 (0)1275 870078 Fax: +44 (0)1275 343453 Email: menvier.security@dial.pipex.com Internet: http//:www.menviersecurity.co.uk 18606 Drg No. 33:2159:00 Issue 01 Doc.