Owner`s manual

REMOTE CONTROL UPGRAGE KIT -DXV35 DT3
INSTALLATION INSTRUCTIONS
Page 28 of
32
INLET TAP
OUTLET TAP
LP GAS PRESSURE REQUIREMENTS
Inlet and manifold gas pressure checking taps are located on gas valve. These ports are only accessible from the outer
left side of the fireplace. A qualified installer shall take pressure measurements at these ports to verify and set the correct
gas pressures during the LP Kit installation and before fascia materials are installed over the front of this fireplace.
Manifold pressure must
be taken at the “MANIFOLD PRESSURE" tap and inlet pressure at the "INLET PRESSURE" tap
with the burner operating by a qualified installer.
DESIRED
INLET
PRESSURE
MINIMUM
INLET
PRESSURE
MAXIMUM
INLET
PRESSURE
MANIFOLD
OUTLET
PRESSURE
AIR SHUTTER
POSITION
L.P. GAS 11.0" W.C.
(2.75 kPa)
11" W.C.
(2.75 kPa)
13.0" W.C.
(3.24 kPa)
10.0" W.C.
(2.5 kPa)
1/4" OPEN
MIN.
(5 mm)
REGULATE THE FLAME HEIGHT TO "HIGH" POSITION. OUTLET GAS PRESSURES MAY VARY PLUS OR MINUS
5%.
LPG PROPER INPUT RATES
With the proper orifices installed, as specified above,
this fireplace utilizing LP Gas will have a maximum
input rate of 31,000 Btu/Hr.
LEAK TESTING REQUIREMENTS
Prior to completing the conversion process, check for
gas leaks with soap and water solution at all plumbing
joints prior to placing this appliance into operation. It
is recommended that all gas-plumbing joints, factory
installed and field installed are checked for leaks.
PILOT FLAME AND MAIN BURNER RELATIONSHIP VERIFICATION
Figure 1: Pressure Test Port
Prior to completing the conversion process, the qualified service technician must, light the pilot light and verify the
relationship between the pilot light flames and the main burners. The pilot light flames directed towards the propagation
ports on the rear and front burner must overlap the propagation ports on the burners. The pilot light flames must be a
minimum of ¾” long and must overlap the propagation ports on both the rear and front burners as shown in the diagram,
below. Verify that the burner tubes ignite quickly and the burner flames propagate smoothly along the entire length of the
burners.
PILOT FLAME LENGTH ADJUSTMENT
If the pilot light flame length is too short and the system does
not maintain a standing pilot, a qualified installer may increase
the length of the pilot light flames to meet the two
requirements: Minimum pilot light length to maintain a
standing pilot light and the pilot light flames must be long
enough to overlap the front and rear burner ports, 1 inch long
minimum.
1" MIN.
FRONT
BURNER
REAR
BURNER
PILOT LIGHT FLAMES
MUST OVERLAP
BURNER PORTS.