Operating instructions
22
MENDOTA DXV-35 GAS DIRECT VENT FIREPLACE
SPECIFICATIONS & CLEARANCES FOR REAR VENT SYSTEM
area) are permitted.
Adjacent Walls:
FROM TOP
OF GRILL
TO 8" MANTEL
14 MIN.
wall at 45° to the front and starting at the appliance's
IF MANTEL IS MADE OF A NON-COMBUSTIBLE MATERIAL
43 3/16
(BRICK, STONE, ETC..), OR HAS A STEEL PROTECTOR PLATE
ON THE UNDERSIDE IT MAY BE PLACED ANYWHERE ABOVE GRILL
outer edge is permitted. Projections behind this wall (shaded
facing must be at least 10" from the firebox opening. A
A wall, perpendicular to and in front of the appliance front
16 3/32
TRIANGULAR AREA. FOR
COMBUSTIBLE MANTEL
BY 2". MANTEL MAY BE LOWERED
MANTEL DEPTH, INCREASE
DECREASED IN THE SAME MANNER
4 21/32"
GAS INLET
HEARTH PROTECTOR MAY BE REDUCED BY 2".
FOR EVERY 1" THE FIREPLACE IS RAISED OFF THE FLOOR,
IF FIREPLACE IS RAISED 6" OR MORE, NO HEARTH PROTECTION IS REQUIRED.
& MINIMUM
NOTE:
CEILING HEIGHT
HEARTH PROTECTOR
NON-COMBUSTIBLE
REQUIRED
12"
DEPTH
49 1/2" MIN.
ABOVE UNIT
COMBUSTIBLE
CLEARANCE TO
DEPTH (WIDTH)
14" DISTANCE
MINIMUM TO
8" MANTEL
8" MANTEL
1
2
31-1/2
22-5/8
2 7/16"
IF DEPTH IS
8" THIMBLE
& 5"X8"
HORIZONTAL
TERMINATION
CAP
EVERY 1" INCREASE IN
HEIGHT ABOVE GRILL
1 5/32
MUST REMAIN IN THIS
11 1/16
35 31/32
22 9/32
45°
10"
31 15/32
1/2 to
2 1/2
16 3/32
19 19/32
15 13/32
HEIGHT
DEPTH
WIDTH
MINIMUM FRAMING DIMENSIONS
FOR THE DIRECT VENT
(800 mm)
(410 mm)
(943 mm)
37 1/8
31-1/2
16-1/8
2X4 WALL
31 1/2
28 15/16
35 31/32
1 7/8
8" COMBUSTIBLE MANTEL
32
4 3/32 FOR 2X4 WALLS
2 19/32 FOR 2X6 WALLS
44 29/32
6" LENGTH MINIMUM
9" LENGTH MAXIMUM
10 13/16
64 5/32
4 3/32 FOR 2X4 WALLS
2 19/32 FOR 2X6 WALLS
44 29/32
45 Deg L
USE ONLY DURAVENT 5"X8" COAXIAL PIPES AND VENTING COMPONENTS.
USE A MINIMUM OF A 6" DURAVENT PIPE SECTION
TO CONNECT THE REAR VENT STATER COLLAR TO
THE HORIZONTAL CAP. SLIDE HORIZONTAL CAP
OVER THE 6" PIPE AS FAR AS NEEDED.
CORNER INSTALLATION
FOR 2x4 WALLS, USE
THESE DIMENSIONS.
FOR 2X6 WALLS, MOVE
FIREPLACE CLOSER TO
WALLS IN EACH
DIRECTION 2".
USE A 9" PIPE SECTION
IF YOU DESIRE A WIDER
DIAGONAL
MEASUREMENT.
WARNING: Do not cover the 2” faceplate border of the unit with combustible materials.
Figure 7: SPECIFICATIONS AND CLEARANCES FOR DXV35 REAR VENTED SYSTEM ONLY!!
NOTE
: MAXIMUM HORIZONTAL RUN ALLOWED IS 9” FOR STRAIGHT-OUT-THE-BACK AND
CORNER INSTALLATIONS. ONLY THE VENT CONFIGURATIONS SHOW ABOVE ARE ALLOWED!!
NOTE: WHEN INSTALLING THE DXV35 USING THE REAR VENT OPTION AT ALTITUDES ABOVE 4000
FEET, THE
GAS INPUT RATE MUST BE REDUCED (DERATED) BY 4% FOR EVERY 1000 FEET
ABOVE SEA LEVEL. CONTACT YOUR GAS SUPPLIER FOR PROPER DERATING
INSTRUCTIONS.