Operating instructions

26 UP/BP/ULP/SLP 400 - 800
9.4 Segment end command
The programme segments are connected by a segment end command. The end
commands determine the programme flow. They also determine how many programme
segments are displayed during the programming procedure.
"End of the
programme"
Printer(if connected) stops
printing
ϑ
20°C
100°C
t
cool down
programme flow:
A
t the end of the programme the heating is
switched off and all parameters (e.g. fan)
are set to the default value. No further
programme segment accessible.
"Hold all
settings at the
end of the
programme”
ϑ
20°C
100°C
t
hold
Printer (if connected) continues.
programme flow:
The parameters of the last segment are
held at the end of the programme. No
further programme segment accessible.
"Loop function"
ϑ
20°C
100°
t
repeat
A connected printer moves on.
programme flow:
The programme is repeated n times (n =
1 … 99).
LP. 1 x .... LP. 99 x
the number of the repetitions can be set
in the menu item LP:
LP.CONT
continuous programme repetition until the
programme is stopped manually.
"SETPOINT
WAIT" = wait
for the setpoint
temperature
ϑ
100°C
20°C
2h
t
wait-
tin
g
set temperature
actual temperature
A connected printer moves on.
programme flow:
A
t the end of the present segment, the
programme waits until the set
temperature is reached. Then the
programme then continues with the next
segment. The next programme segment
can be programmed.
"Go to the
next
programme
segment"
ϑ
100°C
20°C
2h
t
set temperature
actual temperature
A connected printer moves on.
programme flow:
A
t the end of the present segment, the
next programme segment follows
immediately. The next programme
segment can be programmed.