4.4.1.3. PC-NET from SYS 500 8.x
If the needed protocols can be found from the list presented in Section 4.4.
Communication units, the upgrading of the DCP-MUX unit to PC-NET should be
possible. The DCP-MUX card is replaced with a multi-port serial card having
sufficient amount of COM-ports. The connected RS232-devices like modems can
usually be used as such. The existing line and station attribute configuration must be
converted to a SCIL script if the DCP-MUX has been configured with a NETCONF
program.
4.4.2. IEC 61850
Migration of Communication Engineering Tool (CET)
configurations before usage
If the IEC 61850 CET project has been originally made with SYS 600 revision 9.0
or 9.1, and the appropriate configuration will be now taken in use in SYS 600
revision 9.2, the following steps are needed to migrate the project.
Before installing the SYS 600 revision 9.2 take a copy of your {guid}.xml files. For
example:
23a247e6-7552-4c58-a202-eff8693f372f.xml from drive>:\sc\prog
\61850_OPC_Server\CET\bin\Tools\OPCSCLExport.
After finalising the SYS 600 revision 9.2 installation, create both a new database
and an IEC 61850 OPC Server to CET. Use SCLImport tool and import your
existing configuration from the {guid}.xml file. A {guid} example included into
above is an example of such a code, the {guid} in your projects, i.e. related .xml
files differs from the example given above.
To successfully use the CET you will need 'Full Access' access rights to be assigned
for everyone to the following folders:
<drive>:\PCMDATABASES (location depends on Environment Variable
PCMDATADIR )
<drive>:\sc\prog\61850_OPC_Server\CET\bin
<drive>:\sc\prog\61850_OPC_Server\CET\bin\Tools\OPCSCLExport
The reason for this migration is that the CET databases in SYS 600 revision 9.0/9.1
and revision 9.2 are not fully compatible.
When existing CET configurations are taken in use with SYS 600
revision 9.2, it is important to also verify that the correct configuration
attribute values will be taken in use by your IEC 61850 project. See
further information in IEC 61850 System Design manual, chapters
Timeout handling and Troubleshooting.
MicroSCADA Pro
Installation and Administration Manual
SYS 600 9.2SYS 600 9.2
1MRS756115