User`s guide

125
If the online mode does not show all NET nodes which are configured and saved,
most probably the corresponding PC-NET process has not been started and the
notification window (and sys_error.log file) contains related error messages.
3.5.14. Shutting down SYS 600
To stop MicroSCADA:
1. Close all monitors.
2. Open the MicroSCADA Control Panel.
3. Click Stop.
4. The dialog box shown in Fig. 3.5.14.-1 is displayed.
A070494
Fig. 3.5.14.-1 Stopping service confirmatio n dial og box
5. Click Ye s .
6. The dialog box shown in Fig. 3.5.14.-2 is displayed, when the applications have
been closed.
A051228
Fig. 3.5.14.-2 Shutting down SYS 600
7. Click OK.
MicroSCADA can also be stopped using Forced Stop. This function is only to be
used when the MicroSCADA system is not stable and has to be ended fast. However
when the shutdown sequence has started there is no way of changing the operation.
The procedure of closing by force should not take longer than 15 seconds.
Do not shut down the base system computers simply by switching off
the power, because this might damage the MicroSCADA system files.
MicroSCADA Pro
Installation and Administration Manual
SYS 600 9.2SYS 600 9.2
1MRS756115