User`s guide

117
1. Open the SYS 600 Control Panel.
2. Click Admin.
3. Click AutoLogon.
4. The dialog shown in the Fig. 3.5.7.-1, is displayed on the screen.
A051230
Fig. 3.5.7.-1 Automati c logon of SYS 600 Monitor
5. Type the user name and the password.
6. Select Automatic Logon Enabled.
7. Click OK.
Using Automatic Logon might compromise the security of the MicroSCADA
system. To override Automatic Logon, press the SHIFT key during Windows
startup. The user is prompted for the user name and password. If the user logs on as
a different user than was defined for the Automatic Logon, the Automatic Logon
has to be re-enabled from the SYS 600 Control Panel.
3.5.8. Automatically opened MicroSCADA monitors
When MicroSCADA is started, the monitors can be opened automatically, for
example, to the operator workstations.
Predefined MicroSCADA monitors
Predefined monitors (up to 999) can be defined to simplify and automate the startup
of MicroSCADA monitors. The MicroSCADA monitors are defined in the file
monitors.dat located in the \sc\sys\active\sys_ folder of the base system computer.
To define predefined monitors:
1. Edit the monitors.dat file in a text editor. The monitors.dat file is described in the
following section.
2. Copy a monitor definition block of the required type and change the predefined
monitor number to a previously unused number.
3. Modify the block to meet your needs regarding:
*
MicroSCADAmonitor type
*
application
*
logical monitor number
MicroSCADA Pro
Installation and Administration Manual
SYS 600 9.2SYS 600 9.2
1MRS756115