Datasheet

3
MFT1845
Multifunction Tester
SPECFICATIONS
Insulation test
Output voltage -0% +20% at rated load or less
Voltage display ±3% ±3 digits ±0.5% of rated voltage
Short circuit current 1.5 mA nominal test current
Test current on load 1 mA at min pass values of insulation
Insulation accuracy
1000 Volts 10 kΩ ~ 999 MΩ ±3% ±2 digits
500 Volts 10 kΩ ~ 500 MΩ ±3% ±2 digits
>500 MΩ±10% ±4 digits
250 Volts 10 kΩ ~ 250 MΩ ±3% ±2 digits
>250 MΩ ±10% ±4 digits
100 Volts 10 kΩ ~ 100 MΩ ±3% ±2 digits
>100 MΩ ±10% ±4 digits
Resistance and continuity
0.01 Ω ~ 99.9 Ω ±2% ±2 digits
100 Ω ~ 99.9 kΩ ±5% ±2 digits
Open circuit voltage 5 V ±1 V
Test current (0 Ω ~ 2 Ω)
205 mA ±5 mA
15 mA ±5 mA (user selectable)
Loop test
Live to earth/neutral supply
48 V ~ 280 V (45 Hz ~ 65 Hz)
Live to live supply 48 V ~ 500 V (45 Hz ~ 65 Hz)
L-N/L-L tests ±5% ±3 digits
L-E tests
0.1 Ω ~ 39.9 Ω ±5% ±5 digits ± noise margin
40.0 Ω ~ 1000 Ω ±10% ±5 digits
Display range 0.01 Ω ~ 999 Ω
Live to earth PFC range 20 kA
Live to live PSCC range 20 kA
Reference conditions apply
For test environments see service data
RCD tests
Supply up to 100 mA 48 V ~ 480 V (45 Hz ~ 65 Hz)
Supply up to 1 A 48 V ~ 280 V
RCD type Type AC, A, S
Type B (pure dc)
No trip test (1/2xI) –10% ~ –0%
Trip test (1xI, 2xI and 5xI) +0% ~ +10%
Ramp test
Touch voltage (0 ~ 253 V) +5% +15% ±0.5 V
Trip time ±1% ±1 ms
Trip current ±3%
Step increments
VAR (variable RCD selection)
10 mA ~ 50 mA 1 mA steps
50 mA ~ 500 mA 5 mA steps
500 mA ~ 1000 mA 10 mA steps
Supply measurement
Voltage 10 V ~ 600 V
(15 ~ 400 Hz) True RMS
±3% ± 1 V ±2 digits
Phase rotation indication
L1–L2–L3 and L1–L3–L2
Frequency 15 Hz ~ 99 Hz ±0.5% ±1 digit
100 Hz ~ 400 Hz ±2.0% ±2 digits
Frequency resolution 0.1 Hz
Power supply
Batteries IEC LR6 type AA alkaline
(6 cells - supplied)
or 1.2 V NiMH
(rechargeable pack of 6 – supplied)
Mains charger for on-board re-charging (4 hours typical) 12 V car
charger (cigar lighter lead - optional)
Earth / ground test
Resolution 0.01 Ω
Current 0.45 mA or 4.5 mA
Noise rejection 20 V pk/pk (7 V rms)
Max probe resistances Rp and Rc
100 kΩ @ 50 V
5 kΩ @ 25 V
2 and 3 pole method (0.01 Ω ~ 1.999 kΩ)
±2.0% ±5 digits
ART method (1.00 Ω ~ 1.999 kΩ)
±5.0% ±5 digits
Stakeless method (1.00 Ω ~ 199 Ω)
±7.0% ±5 digits
Current
(via optional clamp meter)
±5.0% ±3 digits.
Range 0.1 mA to 200 A ac
Resolution 0.1 mA
mV sensor input
Including temperature (third party module)
±1.0% ±2 digits
Range 0.0 mV to ±199.9 mV dc
Resolution 0.1 mV
Data storage
Capacity: 1000 results
Bluetooth
®
communication