14. Load Test
The front mounted mains plug socket can be used to provide a load to check any energy
measuring equipment monitoring the electric vehicle charging point under test is working/counting
correctly. With the CP state set to either C or D (EV connected and ready to charge) and the PP
state set to any setting except NC, an external load may be connected to the mains plug socket,
with a maximum current of 10A, for short durations. The EVCA210 is protected against overload
by a 10 A fuse.
15. Maintenance
Should the EVCA210 adaptor be used as detailed in this user manual, no special maintenance is
required. However, if functional errors occur during normal operation, contact your local Megger
Repair Centre for assistance.
16. Fuse Replacement
If no voltage is present between the L and N of the 4 mm terminals or between the L and N of the
front mains plug socket when the EVCA210 is connected to the charging point and the charging
point is in charging mode, this may be because the EVCA210 internal fuse has blown.
Prior to replacement of the defective fuse, the EVCA210 adaptor must be disconnected from all
measuring circuits and the connection cable must be disconnected from the charging point.
Use only fuses specified and rated as follows: Ceramic 10 A/250 V (5 mm x 20 mm).
Use of uncertified fuses is prohibited.
If a fuse has blown (due to overload, fault or
misconnection) follow the steps below for
replacement:
1. Unscrew the fuse holder cap using an
appropriate screwdriver.
2. Remove the fuse and replace it with a new one.
3. Replace the fuse holder cap.
If new fuses continue to blow, this may indicate a
fault within the EVCA210 adapter; contact your local
Megger Repair Centre for service.
www.megger.com EVCA210
13
Load Test